Model
/Option
12 VDC NGC w/o
Feed-through heater
12 VDC NGC with
Feed-through heater
Model
Recommended
/Option
PS Voltage (V)
12 VDC NGC w/o
14.50
Feed-through heater
12 VDC NGC with
14.50
Feed-through heater
24 VDC NGC w/o
25.00
Feed-through heater
24 VDC NGC with
25.00
Feed-through heater
1 This wire size may require splicing in 12AWG or 2.5mm^2 or smaller wires at each end of the cable to be able to fit screw terminals.
Page 2–20
Table 2–4 12 VDC Battery Power Supply System Maximum Cable Lengths
Min. Batt
1
Voltage
Units
10 AWG
(V)
(ft)
78.28
49.44
12.00
(m)
23.86
15.07
(ft)
38.74
24.47
12.00
(m)
11.81
7.46
Table 2–5 AC Power Supply System Maximum Cable Lengths
(No External Devices connected to NGC, AC Power Supply Only)
1
Units
10 AWG
(ft)
469.67
(m)
143.16
(ft)
232.43
(m)
70.84
(ft)
809.52
(m)
246.74
(ft)
336.97
(m)
102.71
12 AWG
14 AWG
16 AWG
30.97
19.43
9.44
5.92
15.32
9.62
4.67
2.93
12 AWG
14 AWG
16 AWG
296.64
185.81
116.61
90.41
56.63
35.54
146.80
91.95
57.71
44.74
28.03
17.59
511.27
320.25
200.98
155.84
97.61
61.26
212.83
133.31
83.66
64.87
40.63
25.50
1
1
6 mm^2
4 mm^2
2.5 mm^2
90.03
60.17
37.42
27.44
18.34
11.41
44.55
29.78
18.52
13.58
9.08
5.64
1
1
6 mm^2
4 mm^2
540.20
361.03
224.55
164.65
110.04
68.44
267.33
178.66
111.12
81.48
54.46
33.87
931.07
622.26
387.02
283.79
189.67
117.96
387.57
259.03
161.10
118.13
78.95
49.10
1.5 mm^2
22.92
6.99
11.34
3.46
2.5 mm^2
1.5 mm^2
137.54
41.92
68.06
20.75
237.06
72.26
98.68
30.08
2101510 Rev. AG