GE PACSystems RX7i Cpu Programmer's Reference Manual page 322

Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

SVC_REQ 17 Example 1
In this example, interrupts from input %I00033 are masked. The following values are moved into the
parameter block, which starts at %P00347, on the first scan:
Address
%P00347
Address + 1
%P00348
Address + 2
%P00349
SVC_REQ 17 Example 2
When %T00001 transitions on, alarm
interrupts from input %AI0006 are
masked. The parameter block at
%R00100 is set up on the first scan.
GFK-2950C
1
Interrupts
from input
are masked.
70
Input type is
%I.
33
Offset is 33.
February 2018
Chapter 6. Service Request Function
307