3.4.5.15.
36
COM600 series, Version 5.1
Modbus Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Address
0...65535
Default: 0
Data Format
1 = WORD
2 = Integer
3 = Long MSW First
4 = Long MSW Last
5 = Float MSW First
6 = Float MSW Last
Default: 1
Scale
Default: None
Common
Update Rate
0...60000
Default: 0
Controllable single point (SPC)
Information in the following table applies also to the Internal SPC data object.
Table 3.4.5.15-1 Configurable SPC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPC
Class
Addresses
Control Address
0...65535
Default: 0
Indication Address
0...65535
Default: 0
Common
Description
Indication address.
Data format.
Scale used with measurement information.
Maximum update rate of indication
changes between the OPC server and the
client in milliseconds. The value 0 means
that the server sends all the changes to
the client.
Description
Common data class according to IEC
61850.
Control address.
Indication address.