Self powered/dual powered non-directional overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

2.2

Connecting to the Relay for setting via Reydisp

When Reydisp software is running all available communication ports will automatically be detected.
On the start page tool bar open up the sub-menu 'File' and select 'Connect'.
The 'Connection Manager' window will display all available communication ports. With the preferred port
highlighted select the 'Properties' option and ensure the baud rate and parity match that selected in the relay
settings. Select 'Connect' to initiate the relay-PC connection.
The relay settings can now be configured using the Reydisp software. Please refer to the Reydisp Evolution
Manual for further guidance.
NOTE:
1.
In Reydisp Evolution, verify that "Do NOT Check Communications Connection" is selected in the
Advanced properties.
2.
In Reydisp Evolution, check that the Relay Address is set as "1" in the Relay menu. (this is for
7SR450[1/3]-xGx10-1AA0)
3.
In Reydisp Evolution, check that the Relay Address in the Relay menu is same as that of the Device
address.(for 7SR450[1/2/3/4]-[1/2][G/H/J][A/B][1/2]0-1AA0).
© 2018 Siemens Protection Devices Limited
Figure 2-3
PC Com Port Selection
Chapter 2 - 7SR45 Settings & Instrument Guide