<Step 2> Check the CT satisfies the condition given by table K-3 or K-4 depending on CT types.
Each table has 2 requirements. Both must be satisfied.
<Knee point voltage of CTs is given>
Td [ms]
35
50
75
100
150
V
: Knee point voltage [V]
k
R
: Secondary CT resistance [ohms]
ct
R
: Actual secondary burden [ohms]
2
I
: Maximum secondary fault current
fmax
I
: Maximum secondary load current
Lmax
<Accuracy limit factor of CTs is given>
Td [ms]
35
50
75
100
150
R
=
VA
n
'
R
n'
: Equivalent accuracy limit factor defined by the equation above.
I
: Secondary rated current
n
R
: Rated secondary burden [VA]
VA
R
: Secondary CT resistance [ohms]
ct
R
: Actual secondary burden [ohms]
2
n
: Rated accuracy limit factor
I
: Maximum secondary fault current
fmax
I
: Maximum secondary load current
Lmax
Note : The values in the table are based on the following assumption.
- 100% DC component is superimposed.
- Only one CT is saturated.
- No remnance flux is assumed.
Table K-3 CT Requirement defined by V
Requirement 1
V
≧ I
(R
+ R
)×3
k
fmax
ct
2
V
≧ I
(R
+ R
)×3
k
fmax
ct
2
V
≧ I
(R
+ R
)×4
k
fmax
ct
2
V
≧ I
(R
+ R
)×4
k
fmax
ct
2
V
≧ I
(R
+ R
)×8
k
fmax
ct
2
Table K-4 CT Requirement defined by n'
Requirement 1
n' I
≧ 3.75 × I
n
fmax
n' I
≧ 3.75 × I
n
fmax
n' I
5 × I
n
fmax
n' I
5 × I
n
fmax
n' I
≧ 10 × I
n
fmax
+
2
/
I
R
n
ct
n
+
R
2
ct
 402 
6 F 2 S 0 8 5 0
k
Requirement 2
V
≧ I
(Rct+ R
)×14.4
k
Lmax
2
V
≧ I
(Rct+ R
)×20
k
Lmax
2
V
≧ I
(Rct+ R
)×28.8
k
Lmax
2
V
≧ I
(Rct+ R
)×36.8
k
Lmax
2
V
≧ I
(Rct+ R
)×50.4
k
Lmax
2
Requirement 2
n' I
≧ I
×18
n
Lmax
n' I
≧ I
×25
n
Lmax
n' I
≧ I
×36
n
Lmax
n' I
≧ I
×46
n
Lmax
n' I
≧ I
×63
n
Lmax
(K-1)