MYLOS
Building Automation
®
Forced operation upon bus voltage restoration
This parameter is visible only if the forced operation is activated.
Depending on whether the forced operation object is a 1 bit or 2 bit object, two different types of programming are
available:
Options for 1 bit:
- inactive
- active
The "active" selection keeps the forced operation active after bus voltage restoration. The output switching position
is defined by the "Contact switching status in forced operation" programming.
With the selection "inactive" the forced operation is disabled and the output works as if it were programmed with
the "Behaviour upon safety end" parameter.
Options for 2 bit:
- "0" inactive
- "2" OFF
- "3" ON
Selecting "'2' OFF" causes the "forced operation" object to be written with the "2" value and the output to be
deactivated.
Selecting "'3' ON" causes the "forced operation" object to be written with the "3" value and the output to be activated.
With the selection "inactive" the forced operation is disabled and the output works as if it were programmed with
the "Behaviour upon safety end" parameter.
14 Commissioning | MYLOS
Building Automation
®
Commissioning