3.3.9.10

Counter block

The "COUNTER" block increments the internal counter value in the event of a positive edge
at the input.
The maximum counter value is 2. The counter value is reset in the event of an overflow:
0 → 1 → 2 → 0
● Counter value 0 → output Q30 active
● Counter value 1 → output Q31 active
● Counter value 2 → output Q32 active
After the controller has been switched on, the counter value is initialized automatically with 0.
You can reset the counter value to 0 via the "reset" input. As long as the "reset" input is
active, the counter value is 0.
3.3.10

Basic parameter editor (as of V1.10)

Description of the function
The parameters determined in a learn run can be set via PROFIdrive or operating menu.
These parameters are called "basic parameters (Page 174)".
The basic parameters editor can be used to perform initial commissioning of a door control
unit only by setting parameters without a learn run.
For example, the parameter set can be determined once for identical door systems. Each
door control unit is configured with this parameter set at the factory. When replacing a door
control unit, the parameter set can be copied from the old controller to the new controller.
It is recommended to determine the basic parameters for a door system once with a learn
run and then to adapt or copy it to other door control units.
When the motor type or the door mechanism are changed, the basic parameters must be
adjusted accordingly.
Basic parameter editor
There is no plausibility check of the basic parameters by the control unit when basic
parameters are changed. Incorrect parameter assignment may result in undesirable travel
behavior of the door. When the moving mass and configured energy limit are changed, the
configured speed is automatically adjusted for the permissible kinetic energy. After
changing the basic parameters, the drive curve parameters must be checked and adjusted
if necessary.
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
WARNING
SIDOOR functions
3.3 Extended functions
83