Direct Inputs And Outputs - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the
RESET ANNUNCIATOR
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the
setting, the
RESET ANNUNCIATOR
command, operand source and manual source. Each individual source of a
its individual operand
RESET OP (OPRD)
operands generates an event in the event record when activated. The setting here selects the operand that activates the
operand. The RESET pushbutton on the front panel or the reset command from the software
RESET ANCTR OP (OPRD)
activates the
RESET ANCTR OP (MNUL)

5.8.6 Direct inputs and outputs

5.8.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(64)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
— This setting allows the user to assign a descriptive name to the direct input.
DIRECT INPUT 1 NAME
— Represents the source of direct input 1. The specified direct input is driven by the device
DIRECT INPUT 1 DEVICE ID
identified here.
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.8.6.2 Direct outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(64)
 DIRECT OUTPUT 1
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
setting. Then the Modbus execute function 05h with operation code 1000h command
FlexLogic operand is activated by the two sources of
RESET ANCTR OP
or
RESET ANCTR OP (MNUL)
operand.
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 0
DIRECT INPUT 1
BIT NUMBER:
0
DIRECT INPUT 1
DEFAULT: Off
DIRECT INPUT 1
EVENTS: Disabled
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
DIRECT OUT 1 NAME:
Dir Out 1
DIRECT OUT 1 OPERAND:
Off
RESET ANNUNCIATOR
to identify the source of the command. Each of these two
Range: up to 12 alphanumeric characters
Range: 0 to 16
Range: 0 to 96
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
Range: up to 12 alphanumeric characters
Range: FlexLogic operand
INPUTS/OUTPUTS
RESET
command also activates
5-191
5