2 PRODUCT DESCRIPTION
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k for –1 to 1 mA range
12 k for 0 to 1 mA range
600  for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
0.001
RS232
Front port:
19.2 kbps, Modbus RTU
RS485
1 rear port:
Up to 115 kbps, Modbus RTU, isolated
together at 36 Vpk
Typical distance:
1200 m
Isolation:
2 kV
ETHERNET (FIBER)
PARAMETER
FIBER TYPE
100MB MULTI-
MODE
Wavelength
1310 nm
Connector
LC
Transmit power
–20 dBm
Receiver sensitivity
–30 dBm
Power budget
10 dB
Maximum input
–14 dBm
power
Typical distance
2 km
Duplex
full/half
Redundancy
yes
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
10 MB, 10/100 MB (auto-detect)
Connector:
RJ45
SNTP clock synchronization error: <10 ms (typical)
GE Multilin
PRECISION TIME PROTOCOL (PTP)
PTP IEEE Std 1588 2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238TM2011
Slave-only ordinary clock
Peer delay measurement mechanism
D30 Line Distance Protection System
2.2 SPECIFICATIONS

2.2.8 COMMUNICATIONS