3.2 WIRING
A 9-pin RS232C serial port is located on the L30 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.
NOTE
3
a) OPTIONS
In addition to the faceplate RS232 port, the L30 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
NOTE
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPE
COM1
9E
RS485
9G
10Base-F and 10Base-T
9H
Redundant 10Base-F
9J
100Base-FX
9K
Redundant 100Base-FX
9L
100Base-FX
9M
Redundant 100Base-FX
9N
10/100Base-T
9P
100Base-FX
9R
Redundant 100Base-FX
9S
Ethernet switch module with two 10/100Base-T and four 100Base-FX ports
3-22
Figure 3–23: RS232 FACEPLATE PORT CONNECTION
L30 Line Current Differential System
3 HARDWARE