ABB COM600 User Manual page 29

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS756703
Station Automation COM600
User's Manual
Name
Disable Sending GI when
master gets ASDU 70
Enable private ASDU handling
Reply Window Size
Command Handling
Command Address
Enable parallel commands
Execute Timeout
Value/Value range
True
False
Default: False
True
False
Default: False
0...100
Default: 10
0...65534
Default: 32000
True
False
Default: True
0...65
Default: 30
IEC 60870-5-101
Master (OPC) 3.3
Description
Sending of the general interrog-
ation command when the mas-
ter receives ASDU 70. When
false, a general interrogation
command is always sent when
the end of initialization mes-
sage (ASDU 70) is received
from the IEC slave. When true,
general interrogation is not sent
automatically when receiving
ASDU 70.
Private ASDU handling. When
true, the private range ASDUs
146, 148 and 160 are handled
as unknown ASDUS. When
false, ASDU 146 handled as
ASDU 30, ASDU 148 handled
as ASDU 31 and ASDU 160
handled as ASDU 37.
Defines how many data items
can be written without a reply
or request from the master.
The object address of the bit-
stream process object in the
OPC Client, where an unrecog-
nized message is handled.
Parallel commands. When this
is true, the sending of parallel
commands is possible. The
control is returned immediately
back to application and the
return status of command must
be checked from the command
termination process object.
When this is false, sending
another command is not pos-
sible before the previous com-
mand has been completed or
the confirmation timeout has
occurred.
The maximum time an execute
command is waited after a
select command.
29