Electrical installation
4.2 Interface description
Table 4- 4
Terminal
X531
X532
X533
X534
X535
X536
NOTICE
Cable cross section
Cable length and cross section might influence the temperature measurement
(10 Ω cable resistance for a PT100, can falsify the measurement result by 10 %).
For cable lengths > 100 m, cables with a cross-section of ≥ 1 mm
NOTICE
The maximum cable length is 300 m and the cables must be shielded.
4.2.4

Meaning of the LEDs on the Terminal Module TM150

Table 4- 5
Meaning of the LEDs on the Terminal Module TM150
LED
Color
RDY
-
Green
Orange
Red
Green/
Red
Green/
orange
or
red/
orange
16
Channel assignment
Channel number [x]
for 1x2, 3 and 4-wires
0
1
2
3
4
5
State
Description
OFF
The electronic power supply is missing or lies outside the
permissible tolerance range.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Continuous light
DRIVE-CLiQ communication is being established.
Continuous light
At least one fault is present in this component. Note:
The LED is activated regardless of whether the corresponding
messages have been reconfigured.
Flashing light
Firmware is being downloaded.
0.5 Hz
Flashing light
Firmware has been downloaded.
2 Hz
Wait for POWER ON.
Flashing light
Detection of the components via LED is activated (p0154).
2 Hz
Note:
Both options depend on the LED status when module recognition
is activated via p0154 = 1.
Channel number [y]
for 2x2 wires
6
7
8
9
10
11
must be used.
2
Terminal Module 150 (TM150)