Siemens SIMATIC S7-1500 Manual page 47

Analog input module ai 8xu/i/rtd/tc st
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Errors/accuracies
Linearity error (in relation to input range), (+/-)
Temperature error (in relation to input range), (+/-) 0.005%/K; for TC typ. T 0.02 +/- %/K
Crosstalk between the inputs, max.
Repeat accuracy in settled state at 25 °C (in rela-
tion to input range), (+/-)
Temperature errors of internal compensation
Operational limit in the entire temperature range
Voltage in relation to input range, (+/-)
Current in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple in relation to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage in relation to input range, (+/-)
Current in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple in relation to input range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series mode interference (peak value of interfer-
ence < rated value of input range), min.
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Diagnostics function
Interrupts
Diagnostic interrupt
Limit interrupt
Diagnostics alarms
Monitoring of supply voltage
Wire break
Overflow/underflow
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
Technical specifications
6ES7531-7KF00-0AB0
0.02%
-80 dB
0.02%
+/-6 °C
0.3%
0.3%
0.3%
Ptxxx Standard: ±1.5 K, Ptxxx Climatic: ±0.5 K,
Nixxx Standard: ±0.5 K, Nixxx Climatic: ±0.3 K
Type B: > 600 °C ±4.6 K, Type E: > -200 °C ±1.5
K, Type J: > -210 °C ±1.9 K, Type K: > -200 °C
±2.4 K, Type N: > -200 °C ±2.9 K, Type R: > 0 °C
±4.7 K, Type S: > 0 °C ±4.6 K, Type T: > -200 °C
±2.4 K
0.1%
0.1%
0.1%
Ptxxx Standard: ±0.7 K, Ptxxx Climatic: ±0.2 K,
Nixxx Standard: ±0.3 K, Nixxx Climatic: ±0.15 K
Type B: > 600 °C ±1.7 K, Type E: > -200 °C ±0.7
K, Type J: > -210 °C ±0.8 K, Type K: > -200 °C
±1.2 K, Type N: > -200 °C ±1.2 K, Type R: > 0 °C
±1.9 K, Type S: > 0 °C ±1.9 K, Type T: > -200 °C
±0.8 K
40 dB
10 V
60 dB
No
Yes
Yes
Yes; two high limits and two low limits each
Yes
Yes; only for 1 ... 5 V, 4 ... 20 mA, TC, R and
RTD
Yes
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents