Commissioning
No.
57, 68...
233 244
This group object is enabled if the additional function Staircase lighting is enabled in X Staircase lighting template (group
x/ballast x) parameter window, p. 122.
This group object is used to activate/deactivate the Staircase lighting function. On deactivation the group or ballast reacts like
a "normal" gateway group or ballast without a Staircase lighting function. The Staircase lighting function can be reactivated
when the gateway receives a telegram with the value 1 via this group object.
Telegram value:
Provided the Staircase lighting function is activated, it is triggered by a telegram with the value 1 on either the Switch or Status
Switch group object.
In the A Output, Group x/Ballast x staircase lighting parameter window you can define whether a Brightness value, Relative
dimming or Scenes telegram interrupts the Staircase lighting function.
57, 68...
233 244
This group object is enabled if the additional function Staircase lighting is enabled in X Staircase lighting template (group
x/ballast x) parameter window, p. 122 and simultaneously, the "Send status via object "Activate fct Staircase lighting/Status"
parameter is set to Yes in the A Output, Group x/Ballast x staircase lighting parameter window.
In this case, the status of the Staircase lighting function is sent via this group object on the KNX in addition to the functions
described above.
Telegram value:
You can define whether the status is sent On change and/or On request.
57, 68...
233 244
This group object is enabled if the additional function Slave is enabled in X Slave template (group x/ballast x) parameter
window, p. 112.
This group object is used to activate/deactivate the Slave function. On deactivation the group or ballast reacts like a "normal"
gateway group or ballast without a Slave function. The Slave function can be reactivated when the gateway receives a
telegram with the value 1 via this group object.
Telegram value:
In the A Output, Group x/Ballast x slave parameter window it is possible to define whether a Brightness value, Relative
dimming or Scenes telegram interrupts the Slave function.
57, 68...
233 244
This group object is enabled if the additional function Slave is enabled in X Slave template (group x/ballast x) parameter
window, p. 112 and simultaneously, the Send status via object "Activate fct Slave/Status" parameter is set to Yes in the
A Output, Group x/Ballast x slave parameter window.
In this case, the status of the Slave function is sent via this group object on the KNX in addition to the functions described
above.
Telegram value:
You can define whether the status is sent On change and/or On request.
206 2CDC507164D0201 | DG/S x.64.1.1
Function
Activate fct Staircase lighting
0 = Staircase lighting is deactivated
1 = Staircase lighting is activated
Depending on the parametrization, Depending on the parametrization, staircase lighting time and
staircase lighting activation can be started simultaneously. However, the pumping up option is not
supported.
Activate fct Staircase lighting/Status
1 = Staircase lighting function active
0 = Staircase lighting function not active
Depending on the parametrization, Depending on the parametrization, staircase lighting time and
staircase lighting activation can be started simultaneously. However, the pumping up option is not
supported.
Activate Function Slave
0 = Slave is deactivated
1 = Slave is activated and started
Activate fct Slave/Status
1 = Slave function active
0 = Slave function not active
Group object name
Output A - Group x
Output A - Ballast x
Output A - Group x
Output A - Ballast x
Output A - Group x
Output A - Ballast x
Output A - Group x
Output A - Ballast x
Data type
Flags
1 bit
C, W
DPT 1.003
1 bit
C, R, W, T
DPT 1.003
1 bit
C, W
DPT 1.003
1 bit
C, R, W, T
DPT 1.003