Open Channel Monitoring (Ocm) - Siemens sitrans PROBE LU Instruction Manual

2-wire loop powered ultrasonic transmitter for level, volume and flow monitoring of liquids
Hide thumbs Also See for sitrans PROBE LU:
Table of Contents

Advertisement

Open Channel Monitoring (OCM)

OCM converts a level reading (head) into a flow value using a linear algorithm.
SITRANS Probe LU can convert a head level measurement into a flow rate, using an
eleven breakpoint head-versus-flow characteristic curve. This chart is usually available
from the manufacturer of the v-notch weir, Parshall flume, or other open channel device.
Parameter P050 must be set to 9 (universal linear function), and breakpoints must be set
for head levels and corresponding flowrates at parameters P054 and P055. Once these
parameters are set, the mA output is scaled to represent the flowrate, and the RUN mode
display will show the flowrate
Example: Flow Characterization.
11
10
9
8
7
6
5
4
3
2
1
1
2
The maximum and minimum points on the curve must be defined. Then program the
remaining breakpoints to closely match the flow curve of your open channel device.
Page 84
3
4
SITRANS Probe LU – INSTRUCTION MANUAL
5
6
7
8
head (P054)
9
10
11
7ML19985HT01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents