Devices And Range That Can Be Monitored; Access Range; Readable Motion Sfc Programs - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■4. Required hardware
The following hardware is required.
Data storage (Such as an SD card and USB memory)
14.2.2

Devices and range that can be monitored

The following table lists the devices and the ranges that can be monitored with the motion SFC monitor.
(○: Possible, ×: Inapplicable)
Device
Input relay (X/PX)
Output relay (Y/PY)
Internal relay (M)
Special relay (M)
Latch relay (L)
Link relay (B)
Annunciator (F)
Special relay (SM)
Data register (D)
Special register (D)
Link register (W)
Special register (SD)
*1
Motion register (#)
Coasting timer (FT)
Multiple CPU area device (U3E□\G)
*1
To monitor the motion register, the following should be set in the [Controller Setting] dialog box of GT Designer3 (GOT2000).
• Select a type compatible to the motion controller to be used in the [Controller Type] of the CH to connect the motion controller.
For the setting methods of the [Controller Setting] dialog box and the types compatible to motion controller CPUs, refer to the
following.
14.2.3

Access range

The access range is the same as the access range when the GOT is connected to a controller.
For details of the access range, refer to the following.
GOT2000 Series Connection Manual (Mitsubishi Products) For GT Works3 Version1
14.2.4

Readable motion SFC programs

Motion SFC monitor can read the following programs.
• Control codes (SFC diagram. F/FS and G)
• Text (F/FS and G)
Device range
X0 to 1FFF
Y0 to 1FFF
M0 to 12287
M9000 to 9255
L0 to 8191
B0 to 1FFF
F0 to 2047
SM0 to 2255
D0 to 8191
D9000 to 9255
W0 to 1FFF
SD0 to 2255
#0 to 8191
FT
U3E□\G10000 to 24335
GOT2000 Series Connection Manual (Mitsubishi Products) For GT Works3 Version1
Hardware
Program display
14.2 Specifications
Current value monitor
×
14 - 3
14

Advertisement

Table of Contents
loading