6.1.1
Control Unit 320 (CU320)
LEDs while the Control Unit is booting
The individual statuses during the booting procedure are indicated by means of the
LEDs on the Control Unit.
S The duration of the individual statuses varies.
S If an error occurs, the booting procedure is terminated and the cause is
indicated accordingly via the LEDs.
S Once the unit has been successfully booted, all the LEDs are switched off
briefly.
S Once the unit has been booted, the LEDs are driven via the loaded software.
Refer to the description of the LEDs after booting (see table 6-2).
Table 6-1
Control Unit 320 – description of the LEDs during booting
Load software 1
LED
Reset
Error
Red
RDY
Red
2 Hz
DP1
Red
Red
OPT
Red
Red
MOD
OFF
OFF
Possible causes:
S
CompactFlash Card not installed.
S
Load software 2 has not been installed on the CompactFlash card or
is defective.
Remedy:
Plug the appropriate CompactFlash card with the correct software and
parameters into the unit.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Load software 2
Loaded
Running
Error
file
OFF
OFF
OFF
Red
Red
Orange
2 Hz
Red
Red
Red
OFF
OFF
OFF
S
Diagnostics using LEDs
Error
FW
crc
loaded
OFF
OFF
Red
OFF
0.5 Hz
Red
Red
OFF
OFF
Software on the CompactFlash card
is incomplete or defective.
S
CRC invalid.
Diagnosis
Firmware
Initiali-
Running
zing
OFF
OFF
See
See
table 6-2
OFF
OFF
6-191