Connecting DNP3 I/O modules (Low Voltage)

DNP3 I/O module (LV) interconnect cabling

178
For a Low Voltage (LV) DNP3 I/O module, connect the:
Interconnect cabling between each DNP3 I/O module, and
Power to the last DNP3 I/O module of the chain.
The DNP3 I/O module interconnect cabling is shown in Figure 70.
Figure 70: Interconnect cabling between each DNP3 I/O module and power (LV)
Cable
To D400 (RTU Master)
GE Part
RTU Master
Number
Cable: D400 (RTU Master)
GE Part Number: 977-0503
IP-Server
977-0503
Standard Cables
DB9 male to
DB9 male
(GE part number
977-0089)
Pin
Function
1
GND
4
+DC1
5
-DC1
6
TX/RX2
7
TX/RX2
Other
Not Used
Cable: GE Part Number
977-0500
To Power Source
To Power Source
After DNP3 I/O modules have been interconnected, you are now ready to connect power
to the DNP3 I/O modules. See "DNP3 I/O module (LV) connection to the Power Source" on
page 179.
APPENDIX B INSTALLING AND CONNECTING DNP3 I/O MODULES
To RTU Master
First DNP I/O
Module
J1
J1
J1
J2
J2
J2
Second DNP I/O
Module
J1
J1
J2
J2
Daisy-chained
to other DNP I/O
Modules
Last DNP I/O
Module
J1
J1
J2
J2