95
410 V
I
=
= 2.7 kA
k2-ph
2
2
(67.66 mohm)
+ (22.19 mohm + 13.94 mohm)
2 ·
The calculated short-circuit current 2.7 kA is higher than the minimum short-circuit current of the drive
gG fuse type OFAF00H160 (2400 A). -> The 500 V gG fuse (ABB Control OFAF00H160) can be used.
Technical data