System Overview
1.7 System data
Ambient conditions
Ambient climatic conditions
Storage
Transportation
Warning
Storage and transportation:
The above-mentioned conditions only apply to components in their original packaging.
Environmental class
Storage
Transportation
Warning
Organic/biological influences
Storage
Transportation
Warning
Degree of contamination
Installation altitude
Approbation
Certification
Modules
Line Modules in booksize format
Rated supply voltage
Active Line Modules in booksize format
Rated pulse frequency
Motor Modules in booksize format
DC link connection voltage
Rated pulse frequency
1-10
Class 1K3 to EN 60 721-3-1
Temperature: -40° C to +70° C
Class 2K4 to EN 60 721-3-2
Temperature: -40° C to +70° C
Max. humidity: 95 % at 40° C
Class 3K3 to EN 60 721-3-3
Relative air humidity 5 to 65 % (annual average,
≦ 80 % above the maximum for 2 months a year.
Avoid splashing water and do not allow condensation or ice
to form
(EN 60 204, Part 1)
Class 1C2 to EN 60 721-3-1
Class 2C2 to EN 60 721-3-2
Class 3C2 to EN 60 721-3-3
Class 1B1 to EN 60 721-3-1
Class 2B1 to EN 60 721-3-2
Class 3B1 to EN 60 721-3-3
2 to EN 60 664-1
Up to 1,000 m above sea level without derating,
>1,000 m to 5,000 m above sea level (see derating
characteristics)
CE (low-voltage and EMC Directives), cULus
(file pos.: E192450, E164110, E70122, and E214113)
3AC 380 V
8 kHz
510 V DC to 750 V DC
4 kHz
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1