Switching Multiple Acceleration/Deceleration; Setting Acc/Dec Patterns - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 27 Switching multiple acceleration/
6. 27. 1
<F502: Acc/Dec pattern 1>
<F506: S-Pattern range at Acc start>
<F507: S-Pattern range at Acc completion>
<F508: S-Pattern range at Dec completion>
<F509: S-Pattern range at Dec start>
4
4
■ Function
You can select acceleration/deceleration patterns suitable for the purpose.
6
■ Parameter setting
Title
F502
9
F506
F507
F508
F509
■ How to select the setting value for <F502>
0: Linear pattern
This is linear acceleration and deceleration, and is a normal Acc/Dec pattern.
Normally, you can use this setting for operation.
6. [Advanced] How to use parameters
deceleration

Setting Acc/Dec patterns

Parameter name
Acc/Dec pattern 1
S-Pattern range at Acc
start
S-Pattern range at Acc
completion
S-Pattern range at Dec
completion
S-Pattern range at Dec
start
F502 : Acc/Dec pattern 1
0: Linear
1: S-Pattern 1
2: S-Pattern 2
Adjustment range
0: Linear
1: S-Pattern 1
2: S-Pattern 2
0-50
0-50
0-50
0-50
6-108
E6582062
STOP
0.0Hz
13:49
Unit
Default setting
0
%
10
%
10
%
10
%
10