Precautions on European Standard Directives

1. CE Marking labeled on the inverter is based on Low Voltage Directive.
2. Adaptability to EMC Directive shall be determined in a complete plant
equipped with the inverter.
3. Inverter's control circuit terminals are only basically insulated (protection
against electric shock I, overvoltage category II, pollution degree 2).
To meet requirements of CE Marking, final product shall be subject to insulation.
4. Power supply input end of the inverter shall be equipped with protection
devices for overcurrent, short circuit and leakage of electricity.
5. Main circuit wiring (L, N, U, V, W) shall be connected with ring-type compression
terminals.
6. The inverter is only used for fixed installation, not for other occasions.
7. Adaptability to Low Voltage Directive for the inverter
①Protection against Electric Shock:
②Overvoltage category:
③Pollution degree: 2
8. The capacity of relay output terminal mark A,B,C is 30V DC, 0.3A.
AAD03011 inverter meets requirements of overvoltage category II stipulated in
EN50178 standard.
A transformer subject to basic insulation shall be installed between inverter and
power supply. The insulated transformer shall use the product in compliance with
EN standard or IEC standard (with basic insulation at least).
Overall system shall meet requirements of overvoltage category III stipulated
in EN50178 standard.
According to EMC regulation, the inverter is not an independent operating unit.
The overall system may not be evaluated based on electro magnetic compatibility,
until the overall system is composed of the inverter and device with filter.