Commissioning The Emu; Environment Monitoring Application - Huawei SmartAX MA5603T Configuration Manual

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
NOTE
----End
Result
Compare the result as tested with the theoretical value of the ONU receive optical power in the
ODN plan. If the difference between the actual value and the theoretical value is larger than 2
dBm, the line may be faulty.
NOTE

1.3.16 Commissioning the EMU

The MA5600T/MA5603T/MA5608T monitors various environment parameters (including the
temperature, humidity, and voltage of the power supply) to ensure that the MA5600T/MA5603T/
MA5608T can work stably in a proper environment. This topic describes how to commission
the environment monitoring unit (EMU).

1.3.16.1 Environment Monitoring Application

This topic describes the environment monitoring applications in different cabinets.
Table 1-22
Table 1-22 Environment monitoring applications in different cabinets
Monitoring Solution
H801ESC Monitoring
Solution
ESCM Monitoring Solution
EPS75-4815AF Monitoring
Solution (PMIB01)
EPS30-4815AF Monitoring
Solution (PMIB01)
GEPS4845 Monitoring
Solution
Issue 01 (2014-04-30)
l If the value on the optical power meter changes within a range of 0.2 dBm, take the average value.
l If the value on the optical power meter changes in a range wider than 0.2 dBm, there is a probability
that the optical fiber is not properly connected, the optical fiber is excessively bent, or the optical fiber
connector is not clean.
l Do not bend the optical fiber. A bent optical fiber may affect the test result.
Generally, the normal range of the receive optical power of a GPON port on the ONU is from -27 dBm to
-8 dBm.
lists the environment monitoring applications in different cabinets.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cabinet Type
N63E-22
-
F01D500
F01S300
F01D500
1 Commissioning
Typical Configuration
l Two MA5600T shelves
l One MA5600T shelf +
one SPL shelf
Use this program when you
need to monitor the ESCM
One MA5600T(MA5603T)
shelf
One MA5603T shelf
One MA5600T(MA5603T)
shelf
83

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartax ma5600tSmartax ma5608t

Table of Contents