A.1 LOGIC OPERANDS
OPERANDS - G650 - MODEL FX - GX
A
INTERNAL SYSTEM STATUS (CONT.)
Programmable Keypad Status (HMI)
LOCAL/REMOTE Operation status LEDs
LOCAL/REMOTE/OFF Selection
HMI Tab Order Selection (Swithgear selection
status in HMI)
HMI Backlight
A-8
I Key
O Key
* Key
F1 Key
F2 Key
LOCAL OPERATION
MODE
OPERATIONS
BLOCKED
CHANGE LOCAL-
REMOTE
CHANGE OP BLOCKED Operations Block-Unblock signal
HMI Tab Order 01
HMI Tab Order 02
...
HMI Tab Order 16
HMI BACKLIGHT ON
HMI BACKLIGHT OFF
G650 Generator Protection & Control System
I key operation (Programmable signal via PLC)
O key operation (Programmable signal via PLC)
* key operation (Programmable signal via PLC)
F1 key operation (Programmable signal via PLC)
F2 key operation (Programmable signal via PLC)
Local/remote status for operations 1 = Local, 0 =
Remote. Selectable through the front pushbutton
(Hardware) and also through communications
(software).
Operations OFF status (1) Command execution block
(operations blocked both in local and remote
.
mode)
Selectable through the front pushbutton
(Hardware) and also through communications
(software).
Changing local-remote status by communications
HMI element 1 selection. 0 = Not selected, 1 =Selected.
The selection is performed through the SEL front key.
When the element 1 has it selection enabled, it can be
commanded through the O and I front keys.
HMI element 2 selection. 0 = Not selected, 1 =Selected.
The selection is performed through the SEL front key.
When the element 2 has it selection enabled, it can be
commanded through the O and I front keys.
...
HMI element 16 selection. 0 = Not selected, 1
=Selected. The selection is performed through the SEL
front key. When the element 16 has it selection enabled,
it can be commanded through the O and I front keys.
"Switching on backlignt" signal (the display is switched
on by communications
"Switching off backlignt" signal (the display is switched
off by communications
APPENDIX A
GEK-113285A