In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (
setting).
5.10 Transducer inputs/outputs
5.10.1 DCmA inputs
SETTINGS TRANSDUCER I/O DCMA INPUTS DCMA INPUT F1(U8)
DCMA INPUT F1
The C70 is provided with optional DCmA capability. This feature is specified as an option at the time of
ordering. See the Order Codes section in chapter 2 for details.
Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-143: Signal flow for direct input and output
DIRECT INPUT 5
DIRECT INPUT 6
DCMA INPUT F1
FUNCTION: Disabled
DCMA INPUT F1 ID:
DCMA Ip 1
DCMA INPUT F1
UNITS: μA
DCMA INPUT F1
RANGE: 0 to -1 mA
DCMA INPUT F1 MIN
VALUE:
0.000
DCMA INPUT F1 MAX
VALUE:
0.000
TRANSDUCER INPUTS/OUTPUTS
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
Range: Disabled, Enabled
Range: up to 20 alphanumeric characters
Range: six alphanumeric characters
Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5
mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m
Range: –9999.999 to +9999.999 in steps of 0.001
Range: –9999.999 to +9999.999 in steps of 0.001