Special Wonderware Logger Messages; Siemens Reptel Errors - Siemens 3964R User Manual

I/o server
Table of Contents

Advertisement

36

Special Wonderware Logger Messages

The following messages may appear in the Wonderware Logger for the I/O Server:
Establish Link Error - Old Error Code 0x2711
Failed to establish the initial link to the COM (CP52x) card via the S3964R protocol.
Response Error - Old Error Code 0x2712
Failed to received the expected initial response from the COM (CP52x) card after the
initial link was established.
Response Format Error - Old Error Code 0x2713
After the initial link was established and the expected initial repose was received, the
subsequent char received was wrong (the subsequent char does not match the format
expected).
Follow on Establish Link Error - Old Error Code 0x2714
Failed on the 'follow on' link establishment.
Response BCC Error - Old Error Code 0x2715
Failed to receive the BCC response from the COM (CP52x) card.
Note Server versions 4.11 or earlier will report Wonderware Logger error numbers
27xx in the following format: CP52X> REPTEL ERROR CODE 2712, SYSSTAT??.
Server version 5.0 and higher will report Wonderware Logger errors in error message
format as displayed above and no longer use the 27xx error number format.

Siemens REPTEL Errors

All Siemens REPTEL errors will be reported in the Wonderware Logger with the
following format:
Siemens CP52xREPTEL Error XXH
XX is the REPTEL error number reported. Please refer to the Siemens CP52X manual
for the detailed REPTEL error listings, descriptions and suggested remedies.