Front Cover; Power Supply Unit (Psu); Operator Interface/ Fascia; Figure 2.5-1 7Sr21 With 3 + 8 Leds In E6 Case - Siemens 7SR21 Manual

Hide thumbs Also See for 7SR21:
Table of Contents

Advertisement

2.3

Front Cover

With the transparent front cover in place the user only has access to the ▼ and TEST/RESET► buttons, via blue
push buttons, allowing all areas of the menu system to be viewed, but preventing setting changes and control
actions. The only 'action' that is permitted is to reset the Fault Data display, latched binary outputs and LEDs by
using the TEST/RESET
2.4

Power Supply Unit (PSU)

The relay PSU can be directly connected to any substation dc system rated from 30V dc to 220V dc.
In the event of the station battery voltage level falling below the relay minimum operating level, the PSU will
automatically switch itself off and latch out – this prevents any PSU overload conditions occurring. The PSU is
reset by switching the auxiliary supply off and on.
2.5

Operator Interface/ Fascia

The operator interface is designed to provide a user-friendly method of controlling, entering settings and retrieving
data from the relay.
The warning and information labels on the relay fascia provide the following information:
Dielectric Test Voltage 2kV
Impulse Test Above 5kV
Caution: Refer to Equipment Documentation
Caution: Risk of Electric Shock
©2010 Siemens Protection Devices Limited
button. The front cover is used to secure the relay assembly in the case.
Figure 2.5
7SR21 with 3 + 8 LEDs in E6 Case
7SR21 & 7SR22 Argus Description of Operation
Chapter 1 Page 15 of 71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7sr22

Table of Contents