PRODUCT SETUP
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP / IEC104 POINT LISTS  BINARY INPUT / MSP POINTS
 BINARY INPUT / MSP
 POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the D30 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP / IEC104 POINT LISTS  ANALOG INPUT / MME
POINTS
 ANALOG INPUT / MME
 POINTS
5
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the D30 is restarted.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are
NOTE
ignored.
5.3.4.12 IEC 61850 protocol
The D30 is provided with optional IEC 61850 communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850. The settings are not accessible from the front panel
of the device.
IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same
criticality as protection element settings. To ensure reliable performance of protection schemes utilizing IEC
NOTE
61850 messaging, route IEC 61850 traffic on a separate port from SCADA communications, or use redundant,
independent ports, and a high speed network recovery method, such as PRP.
5-42
Point: 0
Off
Point: 1
Off
Point: 255
Off
Point: 0
Off
Point: 1
Off
Point: 255
Off
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS