Connecting Diagram - Toshiba MMU-AP0072H2UL Engineering Data Book

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

5
Outdoor unit

5-7. Connecting diagram

5-7-1. Heat recovery
Central control
power supply
1 60 Hz 120 V
(Note)
1. When using a central control, plug in the connector between [U1,U2] and [U3,U4] terminal of the header
unit.
2. Connect the shield of all control wiring to the control ground screw on every unit. (Indoor & Outdoor)
3. Group control.
4. Power supply wiring to be per NEC and local codes.
5. For the control wires connecting indoor units, outdoor units, and between indoor and outdoor units, use 2-
core shielded wires.
6. For additional details, see the individual unit wiring diagrams. (Indoor & Outdoor)
5-7-2. Heat pump
Outdoor unit
power supply
3 60 Hz 208/230 V
3 60 Hz 460 V
W1
Open
Indoor unit
power supply
1 60 Hz 208/230 V
Outdoor unit
power supply
3 60 Hz 208/230 V
3 60 Hz 460 V
W3
W2
7. Control wire and power line wire between FS unit and indoor unit are the accessory parts of FS unit.
(Wire length: 20 ft (6 m)
If the length between indoor and FS unit exceeds 16 ft (5 m), connect by using the connection cable kit sold
separately (RBC-CBK15FUL)
Connect the connector of control wiring on the indoor P.C. board, and so as the power supply wire to L and
N terminals.
8. When connecting the multiple indoor units to a single FS unit, only group control is available.
For the indoor unit, a remote control cannot be individually connected.
82
Outdoor unit (Header unit)
Outdoor unit (Follower unit)
Indoor unit
Flow selector unit (FS unit)
Remote control
Central remote control (option)
Disconnect switch per NEC
Circuit breaker
W1 : Shielded control wiring between indoor and outdoor units
W2 : Shielded control wiring between indoor units
W3 : Shielded control wiring between outdoor units
W4 : Shielded central control wiring