Preventive Maintenance/Parts Replacement; Preventive Maintenance; Parts Replacement; Input/Output Fuse Rating Chart - Toshiba 1400 Series Operation Manual

Toshiba 1400 series; 1400 plus series ups
Table of Contents

Advertisement

7.0

Preventive Maintenance/Parts Replacement

7.1

Preventive Maintenance

Toshiba's 1400 Series of uninterruptible power systems have been designed to provide
years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the
unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
If the atmosphere of the installation site is very dusty, use a vacuum cleaner to
periodically remove dust accumulations from the system.
7.2

Parts Replacement

The following list shows recommended intervals for periodic replacement of certain
UPS parts.
1)
Batteries: In order to maintain system reliability, the UPS unit's batteries
should be replaced once every 3 to 5 years. To ensure reliable operation, all
of the batteries should be replaced at the same time.
2)
Aluminum electrolytic capacitors: Replace once every 5 years.
3)
Fuses: Replace once every 7 years (see output fuse rating chart below).
4)
Cooling fan: Replace once every 3 years.
7.3

Input/Output Fuse Rating Chart

The following chart shows the recommended fuses for all UPS sizes.
Fuse rating
Model
Amp rating
600 VA
15.0A
800 VA
15.0A
1000 VA
15.0A
1200 VA
15.0A
1500 VA
15.0A
2000 VA
15.0A
500 VA Plus
6.25A
750 VA Plus
8.0A
1000 VA Plus
10.0A
1500 VA Plus
15.0A
7 - 1
Fuse model no.
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
Bussman MDL-6.25
Bussman MDL-8
Bussman MDA-10
Bussman MDA-10