Diagnosis
Abnormality
display
or
LED 6 LED 5 LED 4 LED 3 LED 2 LED 1
protection
control
H33
Indoor /
outdoor
misconnection
abnormality
H36
Outdoor gas
pipe
temperature
sensor
abnormality
H97
Outdoor fan
motor
mechanism
lock
H98
Indoor high
pressure
protection
H99
Indoor
operating unit
freeze
protection
F11
4-way valve
switching
abnormality
F17
Indoor standby
units freezing
abnormality
F90
Power factor
correction
(PFC) circuit
protection
F91
Refrigeration
cycle
abnormality
F93
Compressor
abnormal
revolution
F94
Compressor
discharge
pressure
overshoot
protection
F95
Outdoor
cooling high
pressure
protection
Abnormality
Protection
judgement
operation
Continuous
Heating
for 5s
protection
operation only
2 times
happen within
30 minutes
4 times
happen within
30 minutes
3 times
happen within
40 minutes
4 times
happen within
10 minutes
2 times
happen within
20 minutes
4 times
happen within
20 minutes
4 times
happen within
30 minutes
4 times
happen within
20 minutes
51
Problem
Check location
Indoor and outdoor
• Indoor and
rated voltage
outdoor units
different
check
Outdoor gas pipe
• Outdoor gas pipe
temperature sensor
temperature
open or short circuit
sensor lead wire
and connector
Outdoor fan motor
• Outdoor fan
lock or feedback
motor lead wire
abnormal
and connector
• Fan motor lock or
block
Indoor high pressure
• Check indoor
protection (Heating)
heat exchanger
• Air filter dirty
• Air circulation
short circuit
Indoor freeze
• Check indoor
protection (Cooling)
heat exchanger
• Air filter dirty
• Air circulation
short circuit
4-way valve
• 4-way valve
switching abnormal
• Lead wire and
connector.
Wrong wiring and
• Check indoor/
connecting pipe,
outdoor
expansion valve
connection wire
and pipe
leakage, indoor heat
exchanger sensor
• Indoor heat
open circuit
exchanger
sensor lead wire
and connector
• Expansion valve
lead wire and
connector.
Power factor
• Outdoor PCB
correction circuit
faulty
abnormal
Refrigeration cycle
• Insufficient
abnormal
refrigerant or
valve close
Compressor
• Power transistor
abnormal revolution
module faulty or
compressor lock
Compressor
• Check
discharge pressure
refrigeration
overshoot
system
Cooling high
• Check
pressure protection
refrigeration
system
• Outdoor air
circuit