Configuration
2. To advance to the appropriate voltage configuration (to the right), press the On
button (1). The selected voltage configuration LED flashes. Activate the voltage
configuration by pressing the Standby button (2). The previously selected configuration
parameter LED turns off.
NOTE: Only one nominal utility voltage can be configured. When setting voltage configuration
parameters, selecting an On value for any one parameter automatically sets the other three
possibilities to Off.
3. To toggle the Site Wiring Fault option from active to inactive, press the On button (1) to
advance to the Site Wiring Fault LED, then press the Standby button (2).
4. To accept the configuration settings and exit Configure mode, press the Test/Alarm Reset
button (3).
NOTE: If the unit remains idle for two minutes, Configure mode times out and the configuration settings
are not stored.