Resetting All Alarms - Toshiba BMS-TP5121PWE Owner's Manual

Air conditioning control system
Hide thumbs Also See for BMS-TP5121PWE:
Table of Contents

Advertisement

HOW TO OPERATE
Other Settings
Fig. 42-1 Menu Screen
To return to Monitoring screen (A)
Fig. 42-2 Confirmation Message Screen
62
EN-
(continued)
A B
C
(continued)
42

Resetting all alarms

This menu is provided to clear all alarm signals by
transmitting an alarm clear signal to all air
conditioners.
A Push [OPTION]. The Menu screen (Fig. 42-1)
appears.
To return to the Monitoring screen, push [MAIN].
B Push [Reset all alarm]. A confirmation message
appears as shown in the Confirmation Message
screen (Fig. 42-2).
C Push [Yes] to clear alarm signals.
Push [No] to return to the Menu screen
(Fig. 42-1) without clearing alarm signals.