Sanyo Big PACi 18 Series Technical Data & Service Manual

Sanyo Big PACi 18 Series Technical Data & Service Manual

Big pack i dc inverter
Table of Contents

Advertisement

TECHNICAL DATA

&

SERVICE MANUAL

Indoor Unit
Class
18
SPW-
X 4-Way Air Discharge
XDR184GH56(A/B)
Semi-Concealed
X185H
4-Way Air Discharge
SPW-
XM
Semi-Concealed
XM185H
SPW-
K Wall-Mounted
KR184GH56(A/B)
SPW-
T Ceiling-Mounted
TDR184GH56(A/B)
T185H
SPW-
UR184GH56(A/B)
U
Concealed-Duct
U185H
UR184SH56B
U185SHT
SPW-
US
Concealed-Duct
US185H
Concealed-Duct
D
High-Static Pressure
Outdoor Unit (
Class
70
Heat Pump Unit
SPW-
C
(3-phase)
C706VH8
85464849261000
Indoor Unit
4-Way Air Discharge
Semi-Concealed
Wall-Mounted
Ceiling-Mounted
Concealed-Duct
Concealed-Duct
High-Static Pressure
25
36
SPW-
SPW-
XDR254GH56(A/B)
XDR364GH56(A/B)
X255H
X365H
SPW-
KR254GH56(A/B)
SPW-
SPW-
TDR254GH56(A/B)
TDR364GH56(A/B)
T255H
T365H
SPW-
SPW-
UR254GH56(A/B)
UR364GH56(A/B)
U255H
U365H
UR254SH56B
UR364SH56B
U255SHT
U365SHT
)
90
SPW-
C906VH8
Outdoor Unit
SPW-C706VH8, SPW-C906VH8
48
70
SPW-
XDR484GH56(A/B)
X485H
SPW-
TDR484GH56(A/B)
T485H
SPW-
UR484GH56(A/B)
U485H
UR484SH56B
U485SHT
SPW-
D705H
90
SPW-
D905H
SM830161
REFERENCE NO.

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo Big PACi 18 Series

  • Page 1: Technical Data

    TECHNICAL DATA & SERVICE MANUAL Outdoor Unit Indoor Unit 4-Way Air Discharge Semi-Concealed Wall-Mounted Ceiling-Mounted Concealed-Duct Concealed-Duct High-Static Pressure SPW-C706VH8, SPW-C906VH8 Indoor Unit Class SPW- SPW- SPW- SPW- X 4-Way Air Discharge XDR184GH56(A/B) XDR254GH56(A/B) XDR364GH56(A/B) XDR484GH56(A/B) Semi-Concealed X185H X255H X365H X485H 4-Way Air Discharge SPW-...
  • Page 3 <...
  • Page 4: Combination Of Indoor And Outdoor Units

    Combination of Indoor and Outdoor Units SPW-XDR184GH56(A/B)x4/ SPW-XDR254GH56(A/B)x3/ SPW-XDR364GH56(A/B)x2/ SPW-XDR484GH56(A/B)x2/ SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8 SPW-X185Hx4/ SPW-X255Hx3/ SPW-X365Hx2/ SPW-X485Hx2/ SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8 SPW-XDR254GH56(A/B)x4/ SPW-C906VH8 SPW-X255Hx4/ SPW-C906VH8 SPW-XM185Hx4/ SPW-C706VH8 SPW-KR184GH56(A/B)x4/ SPW-KR254GH56(A/B)x3/ SPW-C706VH8 SPW-C706VH8 SPW-KR254GH56(A/B)x4/ SPW-C906VH8 SPW-TDR184GH56(A/B)x4/ SPW-TDR254GH56(A/B)x3/ SPW-TDR364GH56(A/B)x2/ SPW-TDR484GH56(A/B)x2/ SPW-C706VH8 SPW-C706VH8 SPW-C706VH8 SPW-C906VH8 SPW-T185Hx4/...
  • Page 5: Table Of Contents

    —— CONTENTS —— Section 1. SPECIFICATIONS .................... 1-1 1-1. Unit Specifications ......................1-2 1-2. Major Component Specifications..................1-49 1-3. Other Component Specifications..................1-69 1-4. Dimensional Data ......................1-77 1-5. Refrigerant Flow Diagram....................1-92 1-6. Operating Range ......................1-92 1-7.
  • Page 6: Specifications

    1. SPECIFICATIONS 1-1. Unit Specifications....................1-2 4-Way Air Discharge Semi-Concealed Type ..................1-2 Wall-Mounted Type ..........................1-13 Ceiling-Mounted Type ........................... 1-16 Concealed-Duct Type ..........................1-26 1-2. Major Component Specifications ................1-49 (A) Indoor Units ............................. 1-49 (B) Outdoor Units ..........................1-67 1-3.
  • Page 7: Unit Specifications

    Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 8 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 9 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 10 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 11 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 12 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi...
  • Page 13 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi...
  • Page 14 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi...
  • Page 15 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi...
  • Page 16 Wired: RCS-TM80BG / Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi...
  • Page 17 Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
  • Page 18: Wall-Mounted Type

    Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 34 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
  • Page 19 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
  • Page 20 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
  • Page 21: Ceiling-Mounted Type

    Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 22 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 23 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 24 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 25 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 26 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 27 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 28 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 29 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 30 Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
  • Page 31: Concealed-Duct Type

    Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
  • Page 32 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
  • Page 33 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
  • Page 34 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
  • Page 35 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 36 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 37 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 38 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 39 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 40 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 41 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 42 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
  • Page 43 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
  • Page 44 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
  • Page 45 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
  • Page 46 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
  • Page 47 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
  • Page 48 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
  • Page 49 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
  • Page 50 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
  • Page 51 Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 33 / 31, (37 / 35 / 33: Using short circuit connection) Operation sound...
  • Page 52 Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) 25A Male screw (No Drain Pump) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 48 / 47 / 46 Operation sound Outdoor - Hi dB-A Indoor –...
  • Page 53 Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL Refrigerant control – Drain pump (Drain connection) 25A Male screw (No Drain Pump) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 51 / 50 / 49 Operation sound Outdoor - Hi dB-A Indoor –...
  • Page 54: Major Component Specifications

    1-2. Major Component Specifi cations (A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR184GH56 (A/B), X185H MODEL No. SPW-XDR184GH56 (A/B), X185H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Turbo (1...ø460, L140) Fan motor Model...Nominal output DK8-53B280H...50W...
  • Page 55 1-2. Major Component Specifi cations (A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR254GH56 (A/B), X255H MODEL No. SPW-XDR254GH56 (A/B), X255H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Turbo (1...ø460, L140) Fan motor Model...Nominal output DK8-53B280H...50W...
  • Page 56 1-2. Major Component Specifi cations (A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR364GH56 (A/B), X365H MODEL No. SPW-XDR364GH56 (A/B), X365H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Turbo (1...ø460, 200) Fan motor Model...Nominal output DK8-93C280H...90W...
  • Page 57 1-2. Major Component Specifi cations (A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR484GH56 (A/B), X485H MODEL No. SPW-XDR484GH56 (A/B), X485H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Turbo (1...ø460, 200) Fan motor Model...Nominal output DK8-93C280H...90W...
  • Page 58 1-2. Major Component Specifi cations (A) Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XM185H MODEL No. SPW-XM185H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-XM075XH (Microprocessor), POW-XM075XH Fan (Number...diameter, depth) Turbo (1...ø322, L147) Fan motor Model...Nominal output SIC-72FV-D866-1...66W Source 280/340V (DC), 3-phase...
  • Page 59 1-2. Major Component Specifi cations (A) Indoor Units Wall-Mounted Type SPW-KR184GH56 (A/B) MODEL No. SPW-KR184GH56 (A/B) Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y POW-KR74GXH56 (Microprocessor) Fan (Number...diameter, depth) Cross - flow (1...ø90, L746) Fan motor Model...Nominal output UF4Q-31G5P...12W Source 220 - 230 - 240V, single-phase, 50/60Hz...
  • Page 60 1-2. Major Component Specifi cations (A) Indoor Units Wall-Mounted Type SPW-KR254GH56 (A/B) MODEL No. SPW-KR254GH56 (A/B) Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y POW-KR74GXH56 (Microprocessor) Fan (Number...diameter, depth) Cross - flow (1...ø100, L848) Fan motor Model...Nominal output KFT4Q-31A5P-C...27W Source 220 - 230 - 240V, single-phase, 50/60Hz...
  • Page 61 1-2. Major Component Specifi cations (A) Indoor Units Ceiling-Mounted Type SPW-TDR184GH56 (A/B), T185H MODEL No. SPW-TDR184GH56 (A/B), T185H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (2...ø140, L180) Fan motor Model...Nominal output DK8-63C280H...30W Source 280/340V (DC), 3-phase...
  • Page 62 1-2. Major Component Specifi cations (A) Indoor Units Ceiling-Mounted Type SPW-TDR254GH56 (A/B), T255H MODEL No. SPW-TDR254GH56 (A/B), T255H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (3...ø140, L180) Fan motor Model...Nominal output DK8-63D280H...40W Source 280/340V (DC), 3-phase...
  • Page 63 1-2. Major Component Specifi cations (A) Indoor Units Ceiling-Mounted Type SPW-TDR364GH56 (A/B), T365H MODEL No. SPW-TDR364GH56 (A/B), T365H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (4...ø140, L180) Fan motor Model...Nominal output DK8-123C280H...80W Source 280/340V (DC), 3-phase...
  • Page 64 1-2. Major Component Specifi cations (A) Indoor Units Ceiling-Mounted Type SPW-TDR484GH56 (A/B), T485H MODEL No. SPW-TDR484GH56 (A/B), T485H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-SXRP56B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (4...ø140, L180) Fan motor Model...Nominal output DK8-123C280H...80W Source 280/340V (DC), 3-phase...
  • Page 65 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct Type SPW-UR184GH56 (A/B), UR184SH56B, U185H SPW-UR184GH56 (A/B) SPW-UR184SH56B MODEL No. SPW-U185H SPW-U185SHT Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (1...ø190, L200) Fan motor Model...Nominal output SFG4X-51C3P...50W...
  • Page 66 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct Type SPW-UR254GH56 (A/B), UR254SH56B, U255H SPW- SPW- SPW- MODEL No. UR254SH56B UR254GH56(A/B) U255H U255SHT Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (2...ø190, L200) Fan motor Model...Nominal output SFG4X-71C3P...70W...
  • Page 67 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct Type SPW-UR364GH56 (A/B), UR364SH56B, U365H SPW- SPW- SPW- MODEL No. UR364SH56B UR364GH56 (A/B) U365H U365SHT Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (3...ø190, L200) Fan motor Model...Nominal output...
  • Page 68 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct Type SPW-UR484GH56 (A/B), UR484SH56B, U485H SPW- SPW- SPW- MODEL No. UR484SH56B UR484GH56 (A/B) U485H U485SHT Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter, depth) Centrifugal (3...ø190, L200) Fan motor Model...Nominal output...
  • Page 69 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct Type SPW-US185H MODEL No. SPW-US185H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-US075XH (Microprocessor) Fan (Number...diameter, depth) Centrifugal (1...ø190, L200) Fan motor Model...Nominal output DK8-63G280H...60W Source 280 / 340V (DC), 3-phase, 50/60Hz No.
  • Page 70 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct High Static Pressure Type MODEL No. SPW-D705H Source 220 - 230 - 240V, single-phase, 50/60Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter) Centrifugal (2...ø220) Fan motor Model...Nominal output KFC4X-201B5P...180 W Power source 220 - 230 - 240V, single-phase, 50Hz No.
  • Page 71 1-2. Major Component Specifi cations (A) Indoor Units Concealed-Duct High Static Pressure Type MODEL No. SPW-D905H Source 220 - 230 - 240V, single-phase, 50Hz Controller P.C.B. Ass'y CR-UXRP71B-B (Microprocessor) Fan (Number...diameter) Centrifugal (2...ø250) Fan motor Model...Nominal output KFC4X-401B3P...400 W Power source 220 - 230 - 240V, single-phase, 50Hz No.
  • Page 72: (B) Outdoor Units

    1-2. Major Component Specifi cations (B) Outdoor Units SPW-C706VH8 MODEL No. SPW-C706VH8 Source 380-400-415V, 3-phase, 50/60Hz Controller P.C.B. Ass'y CR-C906VH8 (Microprocessor) Control circuit fuse Compressor Model..number C-9RVN273H0K Source 246V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output 4,200 Compressor oil 1,400 C –...
  • Page 73 1-2. Major Component Specifi cations (B) Outdoor Units SPW-C906VH8 MODEL No. SPW-C906VH8 Source 380-400-415V, 3-phase, 50/60Hz Controller P.C.B. Ass'y CR-C906VH8 (Microprocessor) Control circuit fuse Compressor Model..number C-9RVN393H0U Source 282V (DC) / 3-phase / 60Hz (Inverter drive) Nominal output 5,500 Compressor oil 1,900 C –...
  • Page 74: Other Component Specifications

    1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XDR184-484GH56 (A/B), X185-485H SPW-XDR184-484GH56 (A/B) MODEL No. Indoor Unit SPW-X185-485H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C –...
  • Page 75 1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XM185H MODEL No. Indoor Unit SPW-XM185H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil sensor): TH PB2M-41E-S15-1 kΩ...
  • Page 76: Wall-Mounted Type

    1-3. Other Component Specifi cations Wall-Mounted Type SPW-KR184GH56 (A/B) – 254GH56 (A/B) MODEL No. Indoor Unit SPW-KR184GH56 (A/B) – 254GH56 (A/B) Power Transformer ATR-IIK245 Rated Source VAC, Hz AC 230 V , 50/60 Hz S1: 11 V, 1.25 A S2: 14 V, 0.45 A Secondary S3: 20 V, 0.2 A Ω...
  • Page 77: Ceiling-Mounted Type

    1-3. Other Component Specifi cations Ceiling-Mounted Type SPW-TDR184-484GH56 (A/B), T185-485H SPW-TDR184-484GH56 (A/B) MODEL No. Indoor Unit SPW-T185-485H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil sensor): TH PBC-41E-AS4, PBC-41E-AS8-5 kΩ...
  • Page 78: Concealed-Duct Type

    1-3. Other Component Specifi cations Concealed-Duct Type SPW-UR184-484GH56 (A/B), UR184-484SH56B, U185-485H, U185-485SHT SPW-UR184-484GH56 (A/B) SPW-UR184-484SH56B MODEL No. Indoor Unit SPW-U185-485H SPW-U185-485SHT Power Transformer ATR-IL225B-T-R Rated Source VAC, Hz AC 230 V, 50 Hz S1: DC 13.0 V, 1 A Secondary S2: DC 24.0 V, 0.2 A Ω...
  • Page 79 1-3. Other Component Specifi cations Concealed-Duct Type SPW-US185H MODEL No. Indoor Unit SPW-US185H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil sensor): TH PB2M-41E-SI5-1 E1,E2 kΩ...
  • Page 80 1-3. Other Component Specifi cations Outdoor Units SPW-C706VH8 MODEL No. Outdoor Unit SPW-C706VH8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H kΩ...
  • Page 81 1-3. Other Component Specifi cations Outdoor Units SPW-C906VH8 MODEL No. Outdoor Unit SPW-C906VH8 Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 KTM-35D-S1, DTN-C532G3H kΩ...
  • Page 82: Dimensional Data

    1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type 18, 25 Types 860 – 910 Ceiling opening dimensions Suspension bolt pitch 1-77...
  • Page 83 1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (X) Type 36, 48 Types 1-78...
  • Page 84 1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed (XM) Type 18 Type 1-79...
  • Page 85 1-4. Dimensional Data (A) Indoor Units: Wall-Mounted Type 18 Type 7, 9, 12, 18 type Drain and wiring port (ø9.52) Gas tube ø12.7 (length: Approx. 400 mm) LIquid tube ø6.35 (length: Approx. 470 mm) Drain hose VP13 (length: Approx. 450 mm) 25 type 25 Type 1,140...
  • Page 86 1-4. Dimensional Data (A) Indoor Units: Ceiling-Mounted Type Length Type Air intake 1125 1180 36, 48 1540 1595 Ceiling side 27.5 27.5 Unit: mm (Suspension bolt pitch) Rear (Figure shows view from front) Left side Right side (Liquid tubing • Gas tubing) Liquid tubing...
  • Page 87 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type 18 Type SPW-UR184GH56 (A/B), U185H (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø6.35 (liquid tube) Refrigerant gas line ø12.7 Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 32 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150)
  • Page 88 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR254GH56 (A/B), U255H Indoor unit: 25 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) (Use the tube connector) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
  • Page 89 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR364GH56 (A/B), U365H SPW-UR484GH56 (A/B), U485H Indoor unit: 36, 48 Type (Air outlet duct flange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
  • Page 90 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR184SH56B SPW-U185SHT Ceiling Inspection access panel Inspection access (450 x 450) (Field supply) (Flange O.D.) Ø (Hole) Ø (Hole) (Suspension bolt pitch) Refrigerant tubing joint 6.35Flare Ø (liquid tube) Refrigerant tubing joint 12.7Flare Ø...
  • Page 91 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR254SH56B SPW-U255SHT Ceiling Inspection access panel Inspection access (450 x 450) (Field supply) (Flange O.D.) 26 - Ø (Hole) 20 - Ø (Hole) (Suspension bolt pitch) Refrigerant tubing joint 9.52Flare Ø (liquid tube) Refrigerant tubing joint 15.88Flare...
  • Page 92 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (U) Type SPW-UR364SH56B, U365SHT SPW-UR484SH56B, U485SHT Ceiling Inspection access panel Inspection access (450 x 450) (Field supply) (Flange O.D.) 26 - Ø (Hole) 28 - Ø (Hole) Refrigerant tubing joint 9.52Flare (Suspension bolt pitch) Ø...
  • Page 93 1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct (US) Type SPW-US185H 1-88...
  • Page 94 1-4. Dimensional Data (A) Indoor Units: Concealed-Duct High Static Pressure Type (D Type) SPW-D705H SPW-D905H 1170 (Suspension bolt pitch) 4 - 37⋅ 12 (Hole for suspension bolt) 1100 1222 1-89...
  • Page 95 1-4. Dimensional Data (B) Outdoor Unit: SPW-C706VH8 Unit:mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), flared connection (o9.52) Refrigerant tubing (gas tube), flared connection (o19.05) Refrigerant tubing port Electrical wiring port (o16) 2 x o32 holes (holes for drain) Electrical wiring port (o19) Of the 4 o32 holes , use 1 of the 2 holes specified Electrical wiring port (o29)
  • Page 96 1-4. Dimensional Data (B) Outdoor Unit: SPW-C906VH8 Unit:mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), flared connection (o12.7) Refrigerant tubing (gas tube), flared connection (o19.05) Refrigerant tubing port Electrical wiring port (o16) 2 x o32 holes (holes for drain) Electrical wiring port (o19) Of the 4 o32 holes , use 1 of the 2 holes specified Electrical wiring port (o29)
  • Page 97: Refrigerant Flow Diagram

    1-5. Refrigerant Flow Diagram Cooling cycle Heating cycle Outdoor Unit: SPW-C706VH8 Indoor Unit: 18, 25, 36, 70 Types Accumulator Accumulator Compressor Strainer Solenoid Gas line valve service valve (3/4") High pressure ø25.4 (brazing) switch Heat exchanger Check valve 4-way valve Heat Distributor exchanger...
  • Page 98: Capacity Correction Graph According To Temperature Condition

    1-7. Capacity Correction Graph According to Temperature Condition SPW-C706 / 906VH8 Max. Capacity & Input Change Characteristics When the Outdoor Air Temperature Changes : Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) For 50 Hz and 60 Hz For 50 Hz and 60 Hz Indoor air intake temp (WB) Indoor air intake temp (°C DB)
  • Page 99: Noise Criterion Curves

    1-8. Noise Criterion Curves (A) Indoor Units Both 50Hz / 60Hz Strong 4-Way Air Discharge Semi-Concealed Type Weak MODEL SPW-XDR184GH56 (A/B) SPW-XDR254GH56 (A/B) MODEL SPW-X185H SPW-X255H SOUND LEVEL : 34 dB(A) STRONG SOUND LEVEL : 31 dB(A) STRONG MEDIUM 31 dB(A) 29 dB(A) MEDIUM WEAK...
  • Page 100 1-8. Noise Criterion Curves (A) Indoor Units Both 50Hz / 60Hz Strong 4-Way Air Discharge Semi-Concealed Type Weak MODEL SPW-XM185H 41 dB(A) SOUND LEVEL STRONG 33 dB(A) WEAK 1.5 m directly below unit CONDITION NC -50 NC -40 NC -30 Approximate minimum audible NC -20...
  • Page 101: Wall-Mounted Type

    1-8. Noise Criterion Curves Wall-Mounted Type Both 50Hz / 60Hz Strong Weak MODEL SPW-KR254GH56 (A/B) MODEL SPW-KR184GH56 (A/B) SOUND LEVEL : STRONG 38 dB(A) SOUND LEVEL : STRONG 41 dB(A) MEDIUM 34 dB(A) 37 dB(A) MEDIUM WEAK 30 dB(A) WEAK 34 dB(A) 1 m in front at height of 1 m CONDITION...
  • Page 102: Ceiling-Mounted Type

    1-8. Noise Criterion Curves Ceiling-Mounted Type Both 50Hz / 60Hz Strong Weak SPW-TDR184GH56 (A/B) MODEL MODEL SPW-TDR254GH56 (A/B) SPW-T185H SPW-T255H STRONG SOUND LEVEL : STRONG 36 dB(A) SOUND LEVEL : 38 dB(A) WEAK 30 dB(A) WEAK 33 dB(A) CONDITION CONDITION 1 m from front of outlet at height of 1 m 1 m from front of outlet at height of 1 m NC-50...
  • Page 103: Concealed-Duct Type

    1-8. Noise Criterion Curves Concealed-Duct Type Both 50Hz / 60Hz Strong Weak MODEL : SPW-UR254GH56 (A/B) MODEL : SPW-UR184GH56 (A/B) SPW-UR254SH56B SPW-UR184SH56B SPW-U255H SPW-U185H SPW-U255SHT SPW-U185SHT STRONG 30 dB(A), NC 23 / WEAK 25 dB(A), NC 17 SOUND LEVEL : SOUND LEVEL : STRONG 34 dB(A), NC 22 / WEAK 27 dB(A), NC 18 CONDITION : Under the unit 1.5 m...
  • Page 104 1-8. Noise Criterion Curves Concealed-Duct Type Both 50Hz / 60Hz Strong Weak MODEL SPW-US185H 35 dB(A) SOUND LEVEL STRONG 31 dB(A) WEAK 1.5 m directly below unit CONDITION NC-50 NC-40 NC-30 Approximate NC-20 minimum audible limit for continuous noise 125 250 1000 2000 4000...
  • Page 105 1-8. Noise Criterion Curves Concealed-Duct High Static Pressure Type Strong Weak MODEL : SPW-D705H MODEL : SPW-D905H SOUND LEVEL : STRONG 48 dB(A), SOUND LEVEL : STRONG 50 dB(A), CONDITION : WEAK 45 dB(A), CONDITION : WEAK 48 dB(A), CONDITION : Under the unit1.5 m CONDITION : Under the unit1.5 m...
  • Page 106: (B) Outdoor Units

    1-8. Noise Criterion Curves Cooling (B) Outdoor Unit Heating MODEL SPW-C706VH8 MODEL : SPW-C706VH8 SOUND LEVEL 57 dB(A) COOLING SOUND 71 dB(A) POWER LEVEL HEATING 57 dB(A) Cooling 1 m in front at height of 1.5 m CONDITION NC-70 NC-70 NC-60 NC-60 NC-50...
  • Page 107: Indoor Fan Performance

    1-9. Indoor Fan Performance Booster Cable for Concealed-Duct Type Electrical component box If external static pressure is too great (due to long Booster cable extension of ducts, for example), the airflow volume Booster cable motor may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the Fan motor socket following procedure:...
  • Page 108 For Short Circuit Connection The standard (before shipment) external static pressure is shown in the table below. When using with a higher static pressure, it is necessary to change to the high static pressure mode. White Yellow Red External static pressure Standard High static pressure TP6 TP3 TP1...
  • Page 109: Airflow Distance Chart

    1-10. Airfl ow Distance Chart 4-Way Air Discharge Semi-Concealed Type If an ultra long-life fi lter or high performance fi lter (65% by colorimetric method) is installed, the vertical air fl ow distance for heating and cooling will be approximately 0.2 m less than the values shown in the graph below. If a high performance fi...
  • Page 110 SPW-XDR254GH56(A/B), X255H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
  • Page 111 SPW-XDR364GH56(A/B), X365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
  • Page 112 SPW-XDR484GH56(A/B), X485H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
  • Page 113 SPW-XM185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.60 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.60 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30 )
  • Page 114 Wall-Mounted Type SPW-KR184GH56(A/B) Heating : Distribution of wind velocity Heating : Distribution of temperature (Strong wind : (Strong wind : Discharge angle app.60 ) (Rm. temp. app.20 Discharge angle app.60 ) (Rm. temp. app.20 1.5m/s 1.2m/s 0.9m/s 0.3m/s 0.6m/s 0.3m/s Horizontal air flow distance (m) Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
  • Page 115 Ceiling-Mounted Type SPW-TDR184GH56(A/B), T185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity...
  • Page 116 SPW-TDR254/364GH56(A/B), T255/365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.
  • Page 117 SPW-TDR484GH56(A/B), T485H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.
  • Page 118: Intaking Fresh Air Of Semi-Concealed Type And Concealed-Duct Type

    1-11. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
  • Page 119 X, XM Type When an External Air Intake Flange (ø100) is in Use External Air Intake Volume and Resistance and With the External Air Intake Flange Attached Operation Noise Characteristics within the Unit X Type XM Type Duct (ø100) for Connecting the External Air Intake Flange Operation Noise (External Air Intake Only)
  • Page 120: Installation Instructions

    1-12. Installation Instructions Tubing Length (A) Single type During tubing work, try to make both the tubing length (L) Single and the difference in elevation (H1) as short as possible. Refer to Table 1-1. Main tubing L Table 1-1 Tubing Data for Models (Single) Models SPW-C706VH8 SPW-C906VH8...
  • Page 121 (B) Simultaneous operation multi (Twin, Triple, Double-Twin) NO T E Because the indoor units run simultaneously, install them within the same room Table 1-2 Table for Managing Tubing Length and Height Differential Actual Symbol Item Contents length Single Twin Triple Double-Twi n (m ) Maximum...
  • Page 122 Table 1-3 Connection Tube Sizes (Twin, Triple, Double-Twin) Double-Twin distribution tube (L1, L2) Indoor unit connection tube Main tubing (L) Total type capacity of indoor unit connected after ( 1, 2, 3, 4) the branch Type capacity of indoor unit 36 –...
  • Page 123 This unit requires no additional refrigerant CAUTION charge up to tubing length 30 m. In case of more than 30 m, additional refrigerant charge is required. Refer to Tables 1-1 and 1-3. In case of multi type installation, indoor units should be installed within the same room.
  • Page 124: Optional Distribution Joint Kits

    Optional Distribution Joint Kits APR-P160BG: Cooling capacity after distribution is 16.0 kW (54,600 BTU/h) or less. APR-P680BG: Cooling capacity after distribution is more than 16.0 kW (54,600 BTU/h) and less than 68.0 kW (232,000 BTU/h). APR-RTP280AGB: Cooling capacity after distribution is 28.0 kW (95,500 BTU/h) or less. Table 1-5 Distribution Branch Size ( 1, 2, 3, 4) Unit: mm (in.)
  • Page 125 Installing Distribution Joint Kit (for Twin & Double-Twin) (APR-P160BG & APR-P680BG) Horizontal Installation For branching tubes, install 150 mm or longer (including reducer) straight tubing up to the point Horizontal line where the tube branches (or after the point where Indoor unit side the tubes join together).
  • Page 126: Installing Distribution Joint Kit (For Triple)

    Installing Distribution Joint Kit (for Triple) (APR-RTP280AGB) Check the system combination before installing the distribution joints. Three indoor units must be installed within the same room. Use the supplied tube connectors to adjust the tube sizes of the distribution joints. How to Install Distribution Joints Distribution joint insulation material (supplied) Use the supplied distribution joints to complete refrigerant...
  • Page 127: Selecting The Installation Site

    SELECTING THE INSTALLATION SITE CAUTION Ceiling-Mounted Type When moving the unit during or after unpacking, Ceiling make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might Wall exceed 30...
  • Page 128 Installation space Air intake Install the outdoor unit with a sufficient space around the Air intake outdoor unit for operation and maintenance. (1) Obstructions on the left side, right side and rear side (Front side and above the unit are opened). (Fig. 1-7) Air discharge Air discharge Anchor bolts...
  • Page 129 Precautions for Installation in Heavy Snow Areas (1) The platform should be higher than the max. snow depth. (Fig. 1-12) (2) The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
  • Page 130 Dimensions of Air-Discharge Chamber : STK-UFV160E In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Unit: mm Reference diagram for SPW-C706 / 906VH8 Air discharge support (STK-FV140B) Air intake Downward, Left side installation fixture (STK-UFV80E)
  • Page 131 Reference diagram for downward left side installation fixture (field supply) : STK-UFV80E Unit: mm 2-o3.3 protrusion hole (reverse side) Reference diagram for downward right side installation fixture (field supply) : STK-UFV80E Unit: mm 2-o3.3 protrusion hole (reverse side) Cyclic bending 1-126...
  • Page 132 Reference diagram for downward center side installation fixture (field supply) : STK-UFV80E Unit: mm Cyclic bending 32.5 (495) 32.5 Same on reverse side (135) 1-127...
  • Page 133 Reference diagram for upward left side installation fixture (field supply) : STK-UFV160E Unit: mm 10.5 145.5 Reference diagram for upward right side installation fixture (field supply) : STK-UFV160E Unit: mm 10.5 135.5 1-128...
  • Page 134 Reference diagram for upward left side installation fixture (field supply) : STK-UFV160E Unit: mm 561.5 Reference diagram for upward right side installation fixture (field supply) : STK-UFV160E Unit: mm Cyclic bending 1-129...
  • Page 135 Reference diagram for air-discharge chamber (fi eld supply) The models of SPW-C706 / 906VH8 with STK-UFV160E Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation Unit: mm The top and both sides must remain open.
  • Page 136 Dimensions of Wind-proof Duct : STK-DGV280E In snowy regions, if there is concern that snow may enter the wind-proof duct, remove the base of the chamber before using. Reference diagram for SPW-C706 / 906VH8 Air intake Unit: mm intake discharge Air discharge discharge discharge...
  • Page 137: Dimensions Of Snow-Proof Duct

    Dimensions of Snow-proof Duct Reference diagram for SPW-C706 / 906VH8 (295) Unit : mm Air intake Air discharge (227) (303) Air discharge Air discharge Air intake Reference diagram for snow-proof duct (field supply) : STK-BDV160E Unit : mm Unit top, snow-proof duct Unit right side Unit left side Unit front side...
  • Page 138 Reference diagram for snow-proof duct - 1 Space requirements for setting - (1) The models of SPW-C706 / 906VH8 with STK-BDV160E Unit: mm [Obstacle to the rear of unit] [Obstacle to the front of unit] Top is open: Top is open: (1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation...
  • Page 139 Reference diagram for snow-proof duct - 2 Space requirements for setting - (2) The models of SPW-C706 / 906VH8 with STK-BDV160E [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
  • Page 140: How To Install The Outdoor Unit

    HOW TO INSTALL THE OUTDOOR UNIT Drainage Work Installing the Outdoor Unit Follow the procedure below to ensure adequate draining for Use concrete or a similar material to make the base, the outdoor unit. and ensure good drainage. For the drain port dimensions, refer to Fig. 1-14. Ordinarily, ensure a base height of 5 cm or more.
  • Page 141: Electrical Wiring

    ELECTRICAL WIRING Control wiring General Precautions on Wiring (C) Inter-unit (D) Remote control (E) Control wiring between outdoor (1) Before wiring, confirm the rated voltage of the unit as and indoor units) wiring for group control shown on its nameplate, then carry out the wiring closely control wiring following the wiring diagram.
  • Page 142 Wiring System Diagrams (for 3-phase outdoor unit: X, K, T, U and D Types) Indoor unit (No. 1) Power supply Outdoor unit 220 – 240 V, 50/60 Hz* INV unit Ground Power supply 380 – 415 V, 3N, ~ 50/60 Hz Remote controller Ground...
  • Page 143 (for 3-phase outdoor unit: XM, US Types) Indoor unit (No . 1) Power supply Outdoor unit 220 – 240 V, 50/60 Hz INV unit Ground Po wer supply 380 – 415 V, 3 N, ~ 50/60 Hz Remote controller Ground Ground Ground Indoor...
  • Page 144 CAUTION (1) When linking the outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) Otherwise the communication of S-net link system is not performed.
  • Page 145 (5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 1-19) Connect wiring as shown in Section “Wiring System Diagrams”. X, K, T, U, D Types Shielded wire Ground Ground XM, US Types...
  • Page 146: Test Run

    2. TEST RUN 2-1. Preparing for Test Run ......................... 2 -2 X, XM, T, U, US, D Types 2-2. Caution..............................2-2 2-3. Test Run Procedure ..........................2-2 2-4. Items to Check Before the Test Run ...................... 2-3 2-5. Test Run Using the Remote Controller ....................2-3 2-6.
  • Page 147: Preparing For Test Run

    X, XM, T, U, US, D Types 2-2. Caution 2-1. Preparing for Test Run This unit may be used in a single-type refrigerant Before attempting to start the air conditioner, system where 1 outdoor unit is connected to 1 check the following: indoor unit, and also in a system where 1 outdoor (1) All loose matter is removed from the cabinet espe- unit is connected to multiple indoor units...
  • Page 148: Items To Check Before The Test Run

    2-6. Precautions 2-4. Items to Check Before the Test Run Request that the customer be present when the test (1) Turn the remote power switch ON at least 12 run is performed. At this time, explain the operation hours in advance in order to energize the crank manual and have the customer perform the actual case heater.
  • Page 150 2-8. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and mainsub remote controller control. 2-8-1. Basic wiring diagram 1 Single type and simultaneous-operation multi system Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) Be careful to avoid miswiring when connecting the wires.
  • Page 151 2-8-2. Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) A maximum of 8 indoor units can be connected to 1 remote controller.
  • Page 152 (Wiring procedure) (1) Connect the remote controller to the indoor unit re- mote controller wiring terminal plate (1, 2). (Remote controller wiring) (2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way.
  • Page 153 2-8-4. Automatic address setting using the remote 2-8-3. Setting the outdoor unit system addresses controller For basic wiring diagram 2 (Set the system addresses: When the outdoor unit shown in “2-8-2. Basic wiring 1, 2, 3...) diagram 2” is used for group control of multiple units, 8 –...
  • Page 154: System Control

    K Type 2-8-6. Main-sub remote controller control Control using 2 remote controller switches 2-9. Caution Main-sub remote controller control refers to the use of 2 This unit may be used in a single-type refrigerant remote controllers to control 1 or multiple indoor units. system where 1 outdoor unit is connected to 1 (A maximum of 2 remote controllers can be connected.) indoor unit, and also in a system where 1 outdoor...
  • Page 155: Test Run Procedure

    2-10. Test Run Procedure 2-12. Preparation for Test Run 2-12-1. Switching the temperature sensor Recheck the items to check (See 2-11) Temperature sensors are contained in the indoor unit before the test run. and wireless remote controller. One or the other of the temperature sensors is used for operation.
  • Page 156: Test Run

    2-13. Test Run Indoor unit control PCB Using the control unit 2 HP Varistor (black) (1) Change the indoor control unit switch from VA002 “ON” “TEST”. Fuse (0.5A) (The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is stop- ped.) CHK (2P plug) (2) All the indicator lamps blink while the test run is in...
  • Page 157: Table Of Self-Diagnostic Functions And Corrections (K Type)

    2-15. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote controller Indoor unit Group connection Correction display receiver lamp 1:1 connection (Single type) (Simultaneous multi (Field supply) system) Nothing is Nothing is • Indoor operation switch is OFF. •...
  • Page 158: System Control

    2-16. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main/sub remote controller control. 2-16-1. Basic wiring diagram 1 Single type and simultaneous-operation multi system Simultaneous-operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) Be careful to avoid miswiring when connecting the wires.
  • Page 159 2-16-2. Basic wiring diagram 2 Group control (when a central control device is not used) A maximum of 8 indoor units can be connected to a single remote controller. Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system address (refrigerant system address) before turning ON the remote power switch.
  • Page 160 2-16-3. Setting the outdoor unit system addresses 2-16-4. Automatic address setting from the outdoor unit For basic wiring diagram 2 (Set the system addresses: When there are multiple outdoor units as shown in basic 1, 2,...) wiring diagram 2 Outdoor unit control PCB 8 –...
  • Page 161: X, T, U, D Types (For Link Wiring) Caution

    X, T, U, D Types (for Link Wiring) 2-16-6. Indoor unit address setting 2-17. Caution If multiple single-type units are installed in the same room the addresses can be set to prevent signal inter- This unit may be used in a single-type refrigerant ference.
  • Page 162: Test Run Procedure

    2-18. Test Run Procedure 2-19. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case Recheck the items to check (See 2-19) before the test run. heater.
  • Page 163: Table Of Self-Diagnostic Functions And Corrections (X, T, U, D Types)

    2-21. Table of Self-Diagnostic Functions and Corrections (X, T, U, D Types) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous-operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON the Nothing is Nothing is correctly.
  • Page 164: Automatic Address Setting

    2-22. Automatic Address Setting 2-22-1. Basic wiring diagram Link wiring NO T E A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
  • Page 165 Automatic address setting using the remote cont- 2-22-2. Setting outdoor unit system addresses roller For the basic wiring diagram (Set the system addresses: Case 3 1, 2, 3...) If the power can be turned ON separately for the Outdoor unit control PCB 8 –...
  • Page 166: K Type

    2-22-3. Checking indoor unit addresses Check that the 220 – 240 V AC wiring is not connected Use the remote controller to check the addresses of the to the inter-unit control wiring connector terminal. indoor units. Press and hold the button and If 220 –...
  • Page 167: Test Run Procedure

    2-24. Test Run Procedure Recheck the items to check (See 2-11) before the test run. Check the combination (wiring) of (See 2-26-1) indoor and outdoor units. Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit) Turn ON Are multiple outdoor units the indoor used?
  • Page 168: Table Of Self-Diagnostic Functions And Corrections (K Type)

    2-25. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous-operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON the Nothing is Nothing is correctly.
  • Page 169: Automatic Address Setting

    2-26. Automatic Address Setting 2-26-1. Basic wiring diagram Link wiring NO T E A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
  • Page 170 2-26-2. Setting the outdoor unit system addresses System address System address System address 10s digit 1s place For basic wiring diagram (Set the system addresses: (2P DIP switch) (Rotary switch) 1, 2, 3...) Both OFF “0” setting Outdoor unit control PCB 8 –...
  • Page 171 2-26-3. Checking indoor unit addresses Automatic address setting from the outdoor unit (K type) Use the remote controller to check the addresses of the indoor units. Press and hold the button and butt- (1) Turn on the indoor and outdoor unit power for on for 4 seconds or longer (simple settings mode, “ALL”...
  • Page 172: Xm Type (For Link Wiring)

    XM Type (for Link Wiring) 2-28. Test Run Procedure 2-27. Caution This unit may be used in a single-type refrigerant Recheck the items to check system where 1 outdoor unit is connected to 1 in- (See 2-29) before the test run. door unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4 <...
  • Page 173: Items To Check Before The Test Run

    2-29. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater. (2) Fully open the closed valves on the liquid-tube and gas-tube sides. 2-30.
  • Page 174: Table Of Self-Diagnostic Functions And Corrections (Xm Type)

    2-31. Table of Self-Diagnostic Functions and Corrections (XM Type) Cause Wired remote Indoor unit Correction Group connection and simultaneous-operation controller display receiver lamp multi system Remote controller is not connected with indoor Nothing is Connect the remote controller correctly. Nothing is displayed unit correctly.
  • Page 175: Automatic Address Setting

    2-32. Automatic Address Setting 2-32-1. Basic wiring diagram Link wiring NOTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes”...
  • Page 176 Automatic address setting using the remote cont- 2-32-2. Setting outdoor unit system addresses roller For the basic wiring diagram (Set the system addresses: 1, 2, 3...) Case 3 If the power can be turned ON separately for the Outdoor unit control PCB indoor and outdoor units in each system (indoor unit System address rotary switch addresses can be set without running the compressor):...
  • Page 177: Caution For Pump Down

    2-32-3. Checking indoor unit addresses Installing the batteries Use the remote controller to check the addresses of the (1) Press on both sides of the remote controller cover indoor units. Press and hold the button and and slide it downward to remove it. button for 4 seconds or longer (simple settings mode, “ALL”...
  • Page 178 Caution on Pump Down (Refrigerant Recovery) NO T E Pump down cannot be performed when the tubing length exceeds 30m. (There is a possiblilty of generating the actuation of the excessive load protection system.) In this case, collect the refrigerant by the refrigeant collecting system.
  • Page 180: Electrical Data

    3. ELECTRICAL DATA 3-1. Indoor Units (Electric Wiring Diagram, Schematic Diagram) ......... 3-2 4-Way Air Discharge Semi-Concealed Type ................... 3-2 Wall-Mounted Type ..........................3-5 Ceiling-Mounted Type ..........................3-9 Concealed-Duct Type ..........................3-11 Concealed-Duct High-Static Pressure Type .................... 3-19 3-2. Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ......3-23...
  • Page 181: Indoor Units (Electric Wiring Diagram, Schematic Diagram)

    3-1. Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR184 / 254 / 364 / 484GH56 (A/B) SPW-X185 / 255 / 365 / 485H Electric Wiring Diagram...
  • Page 182 3-1. Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR184 / 254 / 364 / 484GH56 (A/B) SPW-X185 / 255 / 365 / 485H Schematic Diagram...
  • Page 183 3-1. Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XM185H Electric Wiring Diagram...
  • Page 184 3-1. Indoor Units Wall-Mounted Type SPW-KR184GH56 Electric Wiring Diagram...
  • Page 185 3-1. Indoor Units Wall-Mounted Type SPW-KR184GH56 Schematic Diagram...
  • Page 186 3-1. Indoor Units Wall-Mounted Type SPW-KR254GH56 Electric Wiring Diagram...
  • Page 187 3-1. Indoor Units Wall-Mounted Type SPW-KR254GH56 Schematic Diagram...
  • Page 188: Ceiling-Mounted Type

    3-1. Indoor Units Ceiling-Mounted Type SPW-TDR184 / 254 / 364 / 484GH56 (A/B) SPW-T185 / 255 / 365 / 485H Electric Wiring Diagram...
  • Page 189 3-1. Indoor Units Ceiling-Mounted Type SPW-TDR184 / 254 / 364 / 484GH56 (A/B) SPW-T185 / 255 / 365 / 485H Schematic Diagram 3-10...
  • Page 190: Concealed-Duct Type

    3-1. Indoor Units Concealed-Duct Type SPW-UR184 / 254 / 364 / 484GH56 (A/B) Electric Wiring Diagram 3-11...
  • Page 191 3-1. Indoor Units Concealed-Duct Type SPW-UR184 / 254 / 364 / 484GH56 (A/B) Schematic Diagram 3-12...
  • Page 192 3-1. Indoor Units Concealed-Duct Type SPW-U185 / 255 / 365 / 485H Electric Wiring Diagram 3-13...
  • Page 193 3-1. Indoor Units Concealed-Duct Type SPW-U185 / 255 / 365 / 485H Schematic Diagram 3-14...
  • Page 194 3-1. Indoor Units Concealed-Duct Type SPW-UR184 / 254 / 364 / 484SH56B SPW-U185 / 255 / 365 / 485SHT Electric Wiring Diagram 3-15...
  • Page 195 3-1. Indoor Units Concealed-Duct Type SPW-UR184 / 254 / 364 / 484SH56B SPW-U185 / 255 / 365 / 485SHT Schematic Diagram 3-16...
  • Page 196 3-1. Indoor Units Concealed-Duct Type SPW-US185H Electric Wiring Diagram 3-17...
  • Page 197 3-1. Indoor Units Concealed-Duct Type SPW-US185H Schematic Diagram 3-18...
  • Page 198: Concealed-Duct High-Static Pressure Type

    3-1. Indoor Units Concealed-Duct High-Static Pressure Type SPW-D705H Electric Wiring Diagram 3-19...
  • Page 199 3-1. Indoor Units Concealed-Duct High-Static Pressure Type SPW-D705H Schematic Diagram 3-20...
  • Page 200 3-1. Indoor Units Concealed-Duct High-Static Pressure Type SPW-D905H Electric Wiring Diagram 3-21...
  • Page 201 3-1. Indoor Units Concealed-Duct High-Static Pressure Type SPW-D905H Schematic Diagram 3-22...
  • Page 202: Outdoor Units (Electric Wiring Diagram, Schematic Diagram)

    3-2. Outdoor Units Electric Wiring Diagram SPW-C706 / 906VH8 3-23...
  • Page 203 3-2. Outdoor Units Schematic Diagram SPW-C706 / 906VH8 3-24...
  • Page 204: Process And Functions

    4. PROCESS AND FUNCTIONS 4-1. Control Functions ....................... 4-2 4-2. Outdoor Unit Control PCB ..................4-8 4-3. Indoor Unit Control PCB Switches and Functions ..........4-11...
  • Page 205: Control Functions

    4-1. Control Functions 1. Indoor Air Temprature Control The thermostat is switched on and off in accordance with T shown below. = (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor)
  • Page 206 2) Maximum and Minimum Frequency Control The compressor's inverter frequency is controlled in accordance with the model and operation mode. The maximum and minimum frequencies for each model are shown in the chart below. There are cases in which frequency is limited with other control functions depending on operational conditions, so operations are not always carried out in accordance with the maximum frequencies listed below.
  • Page 207 5) Heating High-Load Prevention Control The following control is performed in the heating mode in accordance with the indoor heat exchanger temperature max (E1, E2). (See the chart below.) The operational frequency of the compressor is decreased when the temperature enters the "M" zone. The operation frequency is modified every 30 seconds while the temperature remains in this zone (the thermostat is switched off if it continues for 2 minutes).
  • Page 208 7) Discharge Temperature Control The following control is performed to prevent the discharge temperature from rising abnormally in order to protect the inverter compressor. In accordance with the temperature of the discharge sensor TD, such controls are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the compressor.
  • Page 209 Heating Mask Time This refers to the shortest time that heating operations must be performed without defrosting operations being executed. The mask time for this model is 25 minutes. Defrosting operations will not be commenced until the defrosting mask time has elapsed, even if frost adherence has been detected.
  • Page 210 12) Demand Control There are two styles of demand operations available as methods of restraining power consumption. (1) Demand via External Input Demand input from an external source is carried out from the outdoor unit EXCT (CN030) PCB or the outdoor unit's serial/parallel I/O (optional).
  • Page 211: Outdoor Unit Control Pcb

    4-2. Outdoor Unit Control PCB (1) Layout Diagram (CR-C906VH8) Fuse (F101) RC_P (CN039) EXCT (CN030) SILENT (CN037) PUMP DOWN (CN048) A.ADD (CN047) Sensor at upper side of heat exchanger (C2) Sensor at lower side of heat exchanger (C1) Suction temp. (TS) Outdoor air temp.
  • Page 212 4-2. Outdoor Unit Control PCB (CR-C906VH8) (2) Explanation of Functions Auto Address Pin 2P (white): Automatic address setting switch (CN047) If the system address switch (S002: set to 0 at time of shipment) setting is other than “0” (central control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
  • Page 213 Quiet mode plug 2P plug (white): Enables operation in quiet mode. (CN037) The outdoor unit fan and compressor frequencies are subject to limits during operation. Low-noise operation is enabled when the relay is turned ON. (Non-voltage contact "a" ) Example of wiring Relay (field supply) Power Quiet mode External contact...
  • Page 214: Indoor Unit Control Pcb Switches And Functions

    4-3. Indoor Unit Control PCB Switches and Functions [Indoor unit control PCB] T10 (CN61): 6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output EXCT (CN73): 2P plug (RED) / Can be used for demand control.
  • Page 215 4-3. Indoor Unit Control PCB Switches and Functions For AC Fan Motor (CR-UXRP71B-B) EEPROM (IC010) OC (CN040) EMG (CN044) VARISTOR (VA100) JP001 OPTION (CN060) EXCT (CN073) GRL (CN020) DISP (CN072) POWER LED (D002) CHK (CN071) FAN DRIVE (CN032) T10 (CN061) FILTER (CN070) For DC Fan Motor (CR-SXRP56B-B) POWER LED (D002)
  • Page 216 For DC Fan Motor (CR-KRP50A) OPTION (CN014) FAN DRIVE (CN017) T10 (CN015) DISP (CN010) CHK (CN011) VARISTOR (VA002) JP001 EMG (CN018) EEPROM (IC002) EXCT (CN009) OC (CN019) FILTER (CN012) For DC Fan Motor (CR-KRP80A) OC (CN019) EEPROM (IC002) JP001 EMG (CN018) VARISTOR (VA002) CHK (CN011) DISP (CN010)
  • Page 218: Service Procedures

    5. SERVICE PROCEDURES 5-1. Meaning of Alarm Messages ..................5-2 5-2. Contents of LED Display on the Outdoor Unit Control PCB ........5-4 5-3. Symptoms and Parts to Inspect ................5-5 5-4. Details of Alarm Messages ..................5-8 5-5. Table of Thermistor Characteristics ................. 5-14 5-6.
  • Page 219: Meaning Of Alarm Messages

    5-1. Meaning of Alarm Messages 1. Contents of the alarm display on the remote controller Blinking: OFF: Wireless remote controller Lamp display Display Possible cause of malfunction Remote controller is Error in receiving serial communication signal Serial commu- detecting error signal from (Signal from main indoor unit in case of group control) nication errors indoor unit...
  • Page 220 Blinking: OFF: Wireless remote controller Lamp display Display Possible cause of malfunction Ceiling panel connection failure Indoor protection Activation of Fan protective thermostat protective Alter. Float switch device DC fan error. Discharge temperature trouble Outdoor protection Open phase detected, AC power trouble No gas 4-way valve locked High cooling load...
  • Page 221: Contents Of Led Display On The Outdoor Unit Control Pcb

    5-2. Contents of LED Display on the Outdoor Unit Control PCB LED 1 LED 2 Remarks Power ON sequence 1. No communication from indoor units in system If it is not possible to advance to 3, repeats 1 2. Communication received from 1 or more indoor units in system At 3, changes to normal 3.
  • Page 222: Symptoms And Parts To Inspect

    5-3. Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Stops when temp. exceeds Recovery at restart 1. Check refrigerant cycle (gas Abnormal discharge temperature error. leak). Discharge temp. Alarm output on 4 pre-trips.
  • Page 223 Remote Alarm Eliminating Judgement and correction controller Judgement conditions contents condition of alarm alarm display Error in current Inverter halted after alarm Recovery at restart 1. Stops immediately even when detection circuit. detected. operations restarted. AC current value is Layer short on the Alarm output on 4 high, even while consecutive (pre-trips.)
  • Page 224 Remote Alarm Eliminating Judgement and correction controller Judgement conditions contents condition of alarm alarm display Settings failure Main unit in simultaneous Power reset 1. Check inter-unit control operation multi control recovery wiring. 2. Check indoor unit duplicated. (Outdoor unit detected) combination.
  • Page 225: Details Of Alarm Messages

    5-4. Details of Alarm Messages Alarm Details (1) [Alarm “P29”] Start-up failure of the compressor (will not start up) Related parts HIC PCB (Model: [706-type, 906-type] HIC-C1155GDXH8) Outdoor unit control PCB (Model: [706-type, 906-type] CR-C906VH8) Start of defect diagnosis Filter PCB (Model: [706-type, 906-type] FIL-C906VH8) Is the power Improve the power voltage line.
  • Page 226 (2) [Alarm P26] Start-up failure of the compressor (will not start up) Related parts HIC PCB (Model: [706-type, 906-type] HIC-C1155GDXH8) Outdoor unit control PCB (Model: [706-type, 906-type] CR-C906VH8) Start of defect diagnosis Filter PCB (Model: [706-type, 906-type] FIL-C906VH8) Was everything OK when in the diagnosis Implement the same check processes for...
  • Page 227 HIC-C1155GDXH8 (706, 906 Types) HIC + Resistance Between terminals Resistance 200 k or more HIC + HIC – 300 k or more HIC + 300 k or more HIC + 300 k or more HIC + 200 k or more HIC –...
  • Page 228 (4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Start of defect diagnosis Are the connectors CN003, CN005, Correct the connections CN041 and CN042 connected correctly to the outdoor unit control PCB? Does the fan rotate without resistance when spun manually after the connectors Fan motor trouble Replace CN003, CN005, CN041 and CN042 are...
  • Page 229 Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Start of defect diagnosis Are the connectors of the sensor 020 (C2), 021 (C1), 022 (TS), Correct the connections. 023 (TO) and 024 (TD) connected correctly to the outdoor unit control PCB ? Are the characteristics of resistance values of the Replace the sensors C2, C1, TS, TO and TD.
  • Page 230 Sensor Temperature Display Function (Displayed regardless of operation and stop) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. <Check procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer.
  • Page 231: Table Of Thermistor Characteristics

    5-5. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO) Sensor, Intake Temp. (TS) Sensor, Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor -20 -15 -10 Temperature ( C) Temperature ( C) (2) Discharge Temp. (TD) Sensor 90 100 110 Temperature ( C) 5-14...
  • Page 232: How To Remove The Compressor

    5-6. How to Remove the Compressor Pay careful attention to prevent water or foreign objects from entering into the refrigerant tubing when removing or installing the compressor. Removing 1. After collecting the refrigerant in the system, replace nitrogen gas from the service port of the gas tubing valve. 2.
  • Page 233: How To Remove The Electrical Component Box

    5-7. How to Remove the Electrical Component Box Removing 1. Remove the front panel and inspection panel from the outdoor unit. 2. Remove all local wires connected to the electrical component box. 3. Remove the wires (temperature sensor, coils of every sort of valve, pressure switch, fan motor and wires for connecting compressor) connected to the electrical component box in the unit.
  • Page 234: Outdoor Unit Maintenance Remote Control

    6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............... 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ....................... 6-6 6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ..........................
  • Page 235: Overview

    6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings.
  • Page 236: Normal Display Operations And Functions

    6-3. Normal Display Operations and Functions Normal display functions Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below. Interface for outdoor unit maintenance Outdoor unit remote controller (ACC-CR-RCS) control PCB RC (5P, red) Relay connector (2P, white) Special service checker wiring...
  • Page 237 Display (functions) • Use the temperature setting buttons to change the item code. 00 (1) Blinking 8-alarm code display at pre-trip, LED (2) No. of indoor units connected in that refrigerant system Unit. Nos. of connected indoor units in that refrigerant system *2 Operating status of indoor units in that refrigerant system (blinks when alarms occur) *2 Unit Nos.
  • Page 238 *2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon. ● Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon...
  • Page 239: Monitoring Operations: Display Of Indoor Unit And Outdoor Unit Sensor Temperatures

    6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press...
  • Page 240: Monitoring The Outdoor Unit Alarm History: Display Of Outdoor Unit Alarm History

    6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
  • Page 241 List of Item Codes (Some item codes cannot be set due to the type of models.) Item code Parameter Control system schedule Do not set Control system schedule Do not set Control system schedule Do not set Snowfall sensor operation 0 = No sensor, control performed 1 = No sensor, control not performed 2 = Sensor present, control performed...
  • Page 242 Setting mode 2 <Operating procedure> (1) Press and hold the button, button, and button simultaneously for 4 seconds or longer. (2) Use the temperature setting buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time buttons to change the setting data.
  • Page 244: Remote Controller Functions Section

    7. REMOTE CONTROLLER FUNCTIONS SECTION 7-1. Simple Settings Function ..................7-2 7-2. List of Simple Setting Items ..................7-3 7-3. Detailed Settings Function ..................7-4 7-4. List of Detailed Setting Items ..................7-5 7-5. Simple Setting Items....................7-9 7-6. Detaild Setting Items ....................7-12 7-7.
  • Page 245: Simple Settings Function

    7-1. Simple Settings Function • This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group- control indoor unit to which the remote controller used for simple settings is connected. When simple settings mode is engaged, operation stops at the individual or group-control indoor unit to which the remote controller for simple settings is...
  • Page 246: List Of Simple Setting Items

    7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours Filter sign ON time 0002 2,500 hours (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
  • Page 247: Detailed Settings Function

    7-3. Detailed Settings Function • This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
  • Page 248: List Of Detailed Setting Items

    7-4. List of Detailed Setting Items Setting data Item Item code Description Description Description 4-Way Air Discharge 1-Way Air Discharge 2-Way Air Discharge Semi-Concealed 0000 0001 0002 Semi-Concealed (A) Semi-Concealed (S) (X, XM) Concealed-Duct Concealed-Duct High 1-Way Air Discharge 0003 0005 0006 Type...
  • Page 249 Setting data Item code Item Description Forced thermostat ON 0000 5 minutes (1B) time 0001 4 minutes –10°C –010 –9°C –009 Cooling discharge –8°C –008 temperature shift 0010 10°C –10°C –010 –9°C –009 Heating discharge –8°C –008 temperature shift 0010 10°C 0001 ±...
  • Page 250 Setting data Item code Item Description 0000 No forced operation 0001 Forced operation for 1 minute Automatic drain pump operation Continuous operation 0060 None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. Wired remote controller 0000 Not used. (Body sensor is used.) Remote control sensor is used.
  • Page 251 Setting data Item code Item Description DC fan tap Purpose operating mode 0000 Standard Standard (setting at shipment) High ceiling use High ceiling setting 1 (with standard panel) Ultra long-life filter, oil guard panel, ammonia 0001 For low static- deodorizing filter, optical regenerative pressure filter Fan tap setting deodorizing filter...
  • Page 252: Simple Setting Items

    7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
  • Page 253 Item code Item Description Set when using a central control device. Central control address Used when setting the central control address manually from the remote controller. Operating mode priority change Note (1) NOTE (1) Explanation of operation mode priority change Enabled only in 2WAY MULTI heat-pump models.
  • Page 254 When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
  • Page 255: Detailed Setting Items

    7-6. Detaild Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
  • Page 256 Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the Heating limit) which is set from the remote controller or central control device. 22 (Lower limit) remote control The set upper limit must be greater than or equal to the lower limit.
  • Page 257 (Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
  • Page 258 DC Fan Tap Change Procedure <Procedure> Be sure to turn the main power OFF before performing the steps below. (1) Check the optional product that will be used from the table below. Setting No. Optional part name Optional part No. Super long-life filter AFT-LS140A Oil guard panel...
  • Page 259: Remote Controller Servicing Functions

    7-7. Remote Controller Servicing Functions • The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. List of Servicing Functions Functions Description Button operation Reset operation Unit status Operation with forced Press and hold the button for 4 Test run thermostat ON...
  • Page 260 Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. <Procedure> 1 Press and hold the buttons simultaneously for 4 seconds or longer.
  • Page 262: How To Install The Wireless Remote Controller Receiver

    8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER ■ Warning 8-1. Warning about Installation of Receivers ..............8-2 8-2. Warning about Installing Remote Controls .............. 8-2 ■ RCS-SH80BG.WL for 4-Way Cassette (X Type) 8-3. Installing the Receiver Unit ..................8-3 8-4.
  • Page 263: Warning About Installation Of Receivers

    ■ Warning 8-1. Warning about Installation of Receivers The wireless remote uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed. ·...
  • Page 264: Installing The Receiver Unit

    ■ RCS-SH80BG.WL for 4-Way Cassette (X Type) 8-3. Installing the Receiver Unit The receiver can only be installed on the corner indicated in Fig. 8-1, so consider how the panel will face when it is installed on the indoor unit. (1) Remove the air inlet grill.
  • Page 265: Accessories

    8-4. Accessories Accessories Quantity Accessories Quantity Receiver AAA alkaline batteries Users Manual Truss Self-Tapping Screws 4 X 16 Remote Controller Cable clamp Remote Control Holder Clamp fixing screw 4 X 12 8-5. Wiring the Receiver Unit ● Wiring Diagram Indoor Unit Receiver PCB DO112 Terminal Strip for...
  • Page 266: Test Operation

    When 1 indoor unit is operated by 2 remote controls: If a group of units are to be controlled by 2 remote controls; Either of the remotes can be set to main/sub. Main/sub remote controls will work regardless of which indoor unit they are installed to.
  • Page 267: Installing The Receiver Unit

    ■ RCS-TRP80BG.WL for Ceiling Mounted (T Type) 8-9. Installing the Receiver Unit (1) Open the air inlet grille on the side panel, remove the 1 screw and then move it toward the front (direction of the arrow) and remove it. (Fig. 8-8) (2) Wrap the tip of a flat head screwdriver with vinyl tape and then slip it into the side of and under where "...
  • Page 268: Accessories

    8-10. Accessories Accessories Quantity Accessories Quantity Receiver AAA alkaline batteries Users Manual Remote Controller Truss Self-Tapping Screws 4 X 16 Remote Control Holder Cable tie 8-11. Wiring the Receiver Unit ● Wiring Diagram Indoor Unit Receiver PCB CN001 Terminal Strip for White Wiring Remote 2RWhite...
  • Page 269: Test Operation

    When 1 indoor unit is operated by 2 remote controls: If a group of units are to be controlled by 2 remote controls; Either of the remotes can be set to main/sub. Main/sub remote controls will work regardless of which indoor unit they are installed to.
  • Page 270: Accessories

    ■ RCS-BH80BG.WL for XM, U and US Types 8-15. Accessories Accessories Quantity Accessories Quantity Receiver Users Manual (Enclosed 200 mm wiring) Truss Self-Tapping Screws 4 X 16 Remote Controller Machine screws Remote Controller's Holder Wood screws Cable tie AAA alkaline batteries 8-16.
  • Page 271: Wiring The Receiver Unit

    ● When using a receiver that has been installed separately into the ceiling,use the enclosed fittings for installing to a ceiling. (1) Remove the metal plate of the receiver by slipping a flathead screwdriver or the like into the cutout on the bottom. (2) Cut out a hole in the ceiling to match the dimensions of the enclosed template.
  • Page 272: Setting Address Switches

    8-18. Setting Address Switches ● When more than one receiver and remote control are installed in the same room, setting up addresses allows them to avoid interfering with each other. ● Refer to the Users Manual for information on how to change the addresses of the remote controls. ●...
  • Page 273 ■ Common to All Models 8-20. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
  • Page 274: Setting Up Remote Control Functions

    8-22. Setting Up Remote Control Functions The functions of the wireless remote can be set on site. (These settings are saved in nonvolatile memory in the remote control, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
  • Page 275 SANYO Electric Co., Ltd. 200805E DC Printed in Japan...

Table of Contents