Line
Function
Swimming pool (Only with swimming pool kit option)
2056
Generator heating setting
Error
6711
Heat pump Reset
Maintenance / special mode
7141
Emergency operation
Off: The heat pump does not use the backup electrical heating system or the boiler connection when a fault
occurs (error 370)
ON: The heat pump uses the backup electrical system or the boiler connection when a fault occurs (error
370). In the "ON" position, the energy costs can be huge if the error is not eliminated.
Diagnostics heat generation
8410
Heat pump return temperature
Setpoint (flow) HP
8412
Heat pump flow temperature
Setpoint (flow) HP
8413
Compressor modulation
Diagnostics consumers
8700
External temperature
8701
Minimum external temperature
Reset ? (no, yes)
8702
Maximum external temperature
Reset ? (no, yes)
8721
Room temperature
8740
Room temperature 1
Ambient temperature setting 1
8743
Flow temperature 1
Flow temperature setpoint 1
8756
Cooling flow temperature 1
Cooling flow temperature setpoint 1
8770
Room temperature 2
Ambient temperature setpoint 2
8773
Flow temperature 2
Flow temperature setpoint 2
8830
DHW (domestic hot water) temperature
DHW temperature setpoint
8900
Swimming pool temperature
Swimming pool temperature setpoint
14
Setting range or
display
8... 35 °C
No, yes
Off, ON
0 ... 140 °C
0 ... 140 °C
0 ... 140 °C
0 ... 140 °C
0 ... 100%
-50 .. 50 °C
-50 .. 50 °C
-50 .. 50 °C
0 .. 50 °C
0 ... 50 °C
4 ... 35 °C
0 ... 140 °C
0 ... 140 °C
0 ... 140 °C
0 ... 140 °C
0 ... 50 °C
4 ... 35 °C
0 ... 140 °C
0 ... 140 °C
0 ... 140 °C
5 ... 80 °C
0 ... 140 °C
0 ... 80 °C
Instruction manual "1353-EN"
B a s i c
Setting
setting
increment
22 °C
No
Off
20 °C
20
50
50
0
0
20
20
50
50
50
24