Functions
PID control
Turn ON X14 to perform PID control. Set 14 in any of [Pr. 178 to Pr. 189].
selection
By turning ON X64, forward action can
PID forward/
be selected for PID reverse action
reverse action
([Pr. 128 = 10, 20]), and reverse action
switchover
for forward action ([Pr. 128 = 11, 21]).
You can input the set point for PID
control.
0 to 5V .............0 to 100%
Set point input
0 to 10V ...........0 to 100%
0 to 20mA ........ 0 to 100%
Set the set point ([Pr. 133]) from the
Set point input
operation panel or parameter unit.
Input the deviation signal calculated
Deviation signal
externally.
-5V to +5V........ -100% to +100%
input
-10 to +10V ...... -100 to +100%
Input the signal from the detector
(measured value signal).
Measured value
4 to 20mA ........ 0 to 100%
input
0 to 5V .............0 to 100%
0 to 10V ...........0 to 100%
Deviation value
Input the deviation value from
input
L
W
ON
Set point,
Input the set point and measured
measured value
value from L
input
communication.
Upper limit output
Lower limit output
"Hi" is output to indicate that the
Forward (reverse)
output indication of the parameter unit
rotation direction
is forward rotation (FWD) or "Low" to
output
indicate that it is reverse rotation
(REV) or stop (STOP).
During PID control
Turns ON during PID control.
activated
PID output
Turns ON when the PID output
interruption
interruption function is performed.
Output terminal
Common terminal for terminals FUP,
common
FDN, RL, PID and SLEEP
W
communication, refer to the L
ON
ORKS
Description
, CC-Link communication.
ORKS
W
, CC-Link
ON
ORKS
W
communication option (FR-A7NL) instruction manual.
ON
ORKS
406
PARAMETER
Parameter Setting
Set 64 in any of [Pr. 178 to Pr. 189].
[Pr. 128 = 20, 21]
[Pr. 133 = 9999]
[Pr. 73 = 1
*1
, 3, 5, 11, 13, 15]
[Pr. 73 = 0, 2, 4, 10, 12, 14]
[Pr. 73 = 6, 7, 16, 17]
[Pr. 128 = 20, 21]
[Pr. 133 = 0 to 100%]
[Pr. 128 = 10
, 11]
*1
[Pr. 73 = 2, 3, 5, 7, 12, 13, 15, 17]
[Pr. 73 = 0, 1
, 4, 6, 10, 11, 14, 16]
*1
[Pr. 128 = 20, 21]
[Pr. 267 = 0
]
*1
[Pr. 267 = 1]
[Pr. 267 = 2]
[Pr. 128 = 50, 51]
[Pr. 128 = 60, 61]
[Pr. 128 = 20, 21, 60, 61]
[Pr. 131
9999]
Set 15 or 115 in any of [Pr. 190 to Pr. 196]
[Pr. 128 = 20, 21, 60, 61]
[Pr. 132
9999]
Set 14 or 114 in any of [Pr. 190 to Pr. 196]
Set 16 or 116 in any of [Pr. 190 to Pr. 196]
Set 47 or 147 in any of [Pr. 190 to Pr. 196]
[Pr. 575
9999]
Set 70 or 170 in any of [Pr. 190 to Pr. 196]
*3
*3
*3
*3