Closing the cycle can avoid indoor freezing.
When the temperature measured by the indoor coil temperature coil is too low, the unit will enter
anti-freezed operation and be set under the below conditions.
Anti-freezed operation start condition:
If accumulative operation time is over 10 minutes at one temperature, the system will make the
thermostat OFF compulsorily until the anti-freezed function can reach stop condition.
Anti-freezed operation stop condition:
The time is over 10 minutes when the temperature rises upto one certain temperature.
2. Dry operation mode
2.1 Temeprature control range: 16~30℃, and control precision: ±1℃
2.2 Characteristic of electronic expansion valve (EEV): as the same as that of cooling mode.
2.3 Fan speed control
Auto: Tr>Ts+1 high speed
Ts+1>Tr≥Ts low speed
Ts>Tr stop fan motor in 3 minutes, 3 minutes later, low speed
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: fan motor stops in 3 minutes, meanwhile the valve goes back to standby angle, and 3
minutes later, it is low speed.
Fan speed adjustment by hand: when unit is running, you can set High/Med/Low/Auto speed due to
request.
2.4 No temperature compensation in Dry mode
2.5 Anti-freezed protection: as the same as that of cooling mode.
3. Heating mode
3.1 Temeprature control range: 16~30℃, and control precision: ±1℃
3.2 Characteristic of electronic expansion valve (EEV): as the same as that of cooling mode, but the
open angle is different.
3.3 Fan speed control
Auto speed:
Heat mode:
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: EEV delays to close, after the fan motor enters super low speed, the thermostat will be
OFF.
TA-TS
+1
0
-1
-2
-106-
>a__WcU[S^ <[c >a`V[e[a`Wc
Super low speed
low speed
med speed
high speed