Hitachi WJ200 Series Quick Reference Manual page 49

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Func.
Code
D007
d008
d009
d010
d012
D013
d014
d015
D016
D017
D018
d022
d023
d024
d025
d026
d027
d029
d030
d050
d060
CALL NOW 800-985-6929
http://www.automatedpt.com
"d" Function
Name
Scaled output frequency
monitor
Actual frequency monitor
Torque command monitor
Torque bias monitor
Output torque monitor
Output voltage monitor
Input power monitor
Watt-hour monitor
Elapsed RUN time monitor
Elapsed power-on time
monitor
Heat sink temperature monitor
Life check monitor
Program counter monitor
[EzSQ]
Program number monitor
[EzSQ]
User monitor 0
[EzSQ]
User monitor 1
[EzSQ]
User monitor 2
[EzSQ]
Positioning command monitor
Current position monitor
Dual monitor
Inverter mode monitor
http://www.automatedpt.com
Description
Displays the output frequency scaled
by the constant in B086.
Decimal point indicates range:
0 to 3999
Displays the actual frequency, range
is -400 to 400 Hz
Displays the torque command, range
is -200 to 200 %
Displays the torque bias value, range
is -200 to 200 %
Displays the output torque, range is
-200 to 200 %
Voltage of output to motor,
Range is 0.0 to 600.0V
Displays the input power, range is 0
to 999.9 kW
Displays watt-hour of the inverter,
range is 0 to 9999000
Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡100 to ⎡999 (10,000 to 99,900)
Displays total time the inverter has
been powered up in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡100 to ⎡999 (10,000 to 99,900)
Temperature of the cooling fin, range
is -20~150
Displays the state of lifetime of
electrolytic capacitors on the PWB
and cooling fan.
Lifetime expired
Normal
Cooling fan
Electrolytic caps
Range is 0 to 1024
Range is 0 to 9999
Result of EzSQ execution, range is
–2147483647~2147483647
Result of EzSQ execution, range is
–2147483647~2147483647
Result of EzSQ execution, range is
–2147483647~2147483647
Displays the positioning command,
range is –268435455~+268435455
Displays the current position, range
is –268435455~+268435455
Displays
two
different
configured in b160 and b161.
Displays currently selected inverter
mode :
I-C:IM CT mode/I-v:IM VT mode/
P:PM
47
Email: charles@automatedpt.com
Run
Units
Mode
Edit
Hz times
constant
Hz
%
%
%
V
KW
hours
hours
°C
data