Temp - GE MDS 4790M Installation And Operation Manual

400 mhz master station radio for mpt 1411 applications
Hide thumbs Also See for MDS 4790M:
Table of Contents

Advertisement

42
Major alarms are displayed first, then minor ones.
The command output displays the event number, major/minor status, and a
one- or two-line text message, respectively. If additional alarm events are
active, the
prompt is displayed.
MORE>
• Press the Enter key to display the next alarm event
• Enter
,
, or
QUIT
Q
The table below gives the text message displayed by the
each associated alarm event.
Table 10. Text Messages of Alarm Event Codes
Event
Number
01
02
03
04
06
07
08
10
12
13
15
16
17
18
20
25
26
27
28
31

TEMP

This command displays the radio's internal temperature in degrees Centigrade.
Note that the radio is designed to operate in a range from –30 C° to +60 C°, and
may fail at temperatures outside this range. This internal reading may be higher
than the outside temperature by several degrees.
MDS 4790M (MPT 1411) I/O Guide
(period) to return to the command prompt.
.
Text Message
Hardware mismatch
Model number not programmed
Authorization fault
Synthesizer out-of-lock
A/D fault
Voltage regulator fault detected
Radio not calibrated
EEPROM write failure
Receiver timeout
Transmitter timeout
Output power fault
Unit address not programmed
Data parity error
Data framing error
Configuration error
10V regulator output not in valid range
DC input power is not in valid range
LNA current is not in valid range
Board current not in valid range
Internal temperature not in valid range
Show Temperature and
Voltages screen, page 62
command for
STAT
MDS 05-3628A01, Rev. B