Differential Pressure Monitor Owner's Manual

Procedure if DOOR SW MODE is set to NOPEN.

1. Verify that DOOR SWITCH = YES.
2. Verify that DOOR SW MODE = NOPEN.
3. Connect the jumper wire between monitor screw terminals 3 and 4 for the
DOOR POSN (Point 32). See Figure 4-1 for location of the screw terminals.
4. Remove the jumper wire from one of the terminals.
5. If DOOR POSN does not toggle OPEN and CLOSED, contact your local Siemens
Building Technologies representative.

Procedure if DOOR SW MODE is set to NCLOSE.

1. Verify that DOOR SWITCH = YES.
2. Verify that DOOR SW MODE = NCLOSE.
3. Connect the jumper wire between monitor screw terminals 3 and 4 for the
DOOR POSN point. See Figure 4-1 for location of the screw terminals.
4. Remove the jumper wire from one of the terminals.
5. If DOOR POSN does not toggle OPEN and CLOSED, contact your local Siemens
Building Technologies representative.
24
Verify that DOOR POSN is OPEN, indicating a contact closure.
Verify that DOOR POSN is CLOSED.
Verify that DOOR POSN is CLOSED, indicating a contact closure.
Verify that DOOR POSN is OPEN.