Mitsubishi Electric MSZ-A09NA Installation Manual

Split-type air conditioners
Hide thumbs Also See for MSZ-A09NA:

Advertisement

Quick Links

MITSUB(SHI
ELECTRIC
SPLIT-TYPE
AIR CONDITIONERS
INSTALLATION
MANUAL
SG79Y952H03
Model names are indicated in 1-3,
When installing multi units, refer to
the installation
manual of the multi
unit for outdoor unit installation.
"
Required
Tools
for |nsta(|ation
1
Phillips screwdriver
5/32 in. (4 mm) hexagonal wrench(
Level
Flare tool for R410A
|
Scale
Gauge manifold for R410A
|
Utility knife or scissors
Vacuum pump for R410A
|
2-9/16 in. (65 mm) hole saw
Charge hose for R410A
|
Torque wrench
Pipe cutter with reamer
|
Wrench (or spanner)
J
1-1. THE FOLLOWING
SHOULD
ALWAYS
BE OBSERVED
FOR SAFETY
• Be sure to read "THE FOLLOWING
SHOULD ALWAYS
BE OBSERVED
FOR SAFETY" before installing the air conditioner.
• Be sure to observe the warnings and cautions specified
here as they include important items related to safety.
• After reading this manual, be sure to keep it together with the OPERATING
INSTRUCTIONS
for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
[] Do not install the unit by yourself
(user).
[] Attach
the electrical cover to the indoor unit and the service panel to the
Incomplete
installation
could cause fire or electric shock, injury due to the unit fall-
ing, or leakage of water. Consult the dealer from whom you purchased the unit or
a qualified
installer.
[] Perform the installation
securely referring
to the installation
manual.
[]
Incomplete
installation
could cause fire or electric shock, injury due to the unit fall-
ing, or leakage of water.
[] Install the unit securely
in a place which
can bear the weight
of the unit.
If the installation
location
cannot bear the weight
of the unit, the unit could fall
[]
causing injury.
[] Perform electrical work according
to the installation manual and be sure to use
an exclusive
circuit.
Do not connect
other electrical
appliances
to the circuit.
[]
If the capacity of the power circuit is insufficient
or there is incomplete
electrical
work, it could result in a fire or an electric shock.
[] Ground
the unit correctly.
Do not connect the ground to a gas pipe, water pipe, lightning
rod or telephone
[]
ground. Defective grounding
could cause electric shock.
[] Do not damage
the wires by applying
excessive
pressure with parts or
screws.
[]
Damaged wires could cause fire.
[] Be sure to cut off the main power in case of setting
up the indoor P.C. board
or wiring
works.
Failure to do so could cause electric shock.
[] Use the specified wires to connect
the indoor and outdoor
units securely
[]
and attach the wires firmly
to the terminal
block connecting
sections
so the
stress of the wires is not applied
to the sections.
Incomplete connecting
and securing
could cause fire.
[] Do not install the unit in a place where inflammable
gas may leak.
If gas leaks and accumulates
in the area around the unit, it could cause an explo-
[]
sion.
[] Do not use intermediate
connection
of the power cord or the extension cord
and do not connect
many devices
to one AC outlet.
[]
It could cause a fire or an electric shock due to defective contact, defective insula-
tion, exceeding the permissible
current, etc.
[] Be sure to use the parts provided or specified
parts for the installation
work.
The use of defective parts could cause an injury or leakage of water due to a fire, an
electric shock, the unit falling, etc.
[] When
plugging the power supply
plug into the outlet,
make sure that there
is
no dust, clogging,
or loose parts in both the outlet
and the plug. Make sure
that the power supply
plug is pushed completely
into the outlet.
If there is dust, clogging, or loose parts on the power supply plug or the outlet, it could
cause electric shock or fire. If loose parts are found on the power supply plug, replace it.
outdoor
unit securely.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
When
installing or relocating
the unit, make sure that no substance
other
than the specified
refrigerant
(R410A) enters the refrigerant
circuit.
Any presence
of foreign substance
such as air can cause abnormal pressure
rise
or an explosion.
Do not discharge the refrigerant
into the atmosphere.
If refrigerant
leaks during
installation,
ventilate the room.
If refrigerant comes in contact with a fire, harmful gas could be generated.
Check that the refrigerant
gas does not leak after installation
has been com-
pleted.
If refrigerant
gas leaks indoors,
and comes
into contact with the flame of a fan
heater, space heater, stove, etc., harmful substances
will be generated.
Use appropriate
tools and piping materials
for installation.
The pressure of R410A is 1.6 times more than R22. Not using appropriate
tools or
materials and incomplete
installation could cause the pipes to burst or injury.
When
pumping down the refrigerant,
stop the compressor
before discon-
necting the refrigerant
pipes.
If the refrigerant
pipes are disconnected
while the compressor
is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration
cycle
could become abnormally
high. This could cause the pipes to burst or injury.
When
installing the unit, securely
connect
the refrigerant
pipes before start_
ing the compressor.
If the compressor
is started before the refrigerant
pipes are connected
and when
the stop valve is open, air could be drawn in and the pressure in the refrigeration
cycle could become abnormally
high. This could cause the pipes to burst or injury.
Fasten a flare nut with a torque
wrench as specified
in this manual.
If fastened too tight, a flare nut may break after a long period and cause refrigerant
leakage.
The unit shall be installed
in accordance
with national wiring
regulations.
[] install a Ground
Fault interrupt (GFI) circuit breaker depending
on the instal-
lation place.
If the Ground Fault Interrupt (GFI) circuit breaker
is not installed,
it could cause
electric shock.
[] Perform the drainage/piping
work securely
according
to the installation
manual.
If there is defect in the drainage/piping
work, water could drop from the unit, soak-
ing and damaging household
goods.
[] Do not touch
the air inlet or the aluminum
fins of the outdoor
unit.
This could cause injury.
[] Do not install the outdoor
unit where small animals
may live.
If small animals enter and touch the electric parts inside the unit, it could cause a
malfunction,
smoke emission,
or fire. Also, advise user to keep the area around
the unit clean.

Advertisement

loading

Summary of Contents for Mitsubishi Electric MSZ-A09NA

  • Page 1 SG79Y952H03 MITSUB(SHI Phillips screwdriver 5/32 in. (4 mm) hexagonal wrench( Level Flare tool for R410A ELECTRIC Scale Gauge manifold for R410A Model names are indicated in 1-3, Utility knife or scissors Vacuum pump for R410A When installing multi units, refer to SPLIT-TYPE AIR CONDITIONERS 2-9/16 in.
  • Page 2: Specifications

    1-2. SELECTING THE INSTALLATION LOCATION me o - Note: Note: Where airflow is not blocked. In rooms where inverter type fluorescent lamps are used, • It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there.
  • Page 3: Installation

    1-4. iNSTALLATION DIAGRAM ACCESSORi Be sure to use wall hole I _/_L/wall hole cover (D) Check the following parts before installation. sleeve (C) to prevent <Indoor unit> Indoor unit _Seal the wall hole indoor/outdoor connecting Installation plate wire (A) from contacting Wall hole ' Vf_]// ..
  • Page 4 2-1. FIXING OF iNSTALLATiON PLATE • Find a structural material (such as a stud) in the wall and fix installation plate (1) horizon- tally with fixing screws (2). • To prevent installation plate (1) from vibrating, be sure to install the fixing screws in the holes indicated in the illustration.
  • Page 5 2-4. PiPE FORMING AND DRAIN PiPiNG 2-4-1. PiPE FORMING • Place the drain hose below the refrigerant piping. Liquid pipe • Make sure that the drain hose is not heaved or snaked. • Do not pull the hose when applying the tape. Gas pipe •...
  • Page 6 3-1. CONNECTING WIRES OUTDOOR UNiT 1 ) Remove the service panel. 2) Remove the conduit cover. 3) Fix the conduit connector to conduit plate (A models)/conduit cover (B models) with lock nut then secure it against unit with screws. 4) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the indoor l in.
  • Page 7 3-3. PiPE CONNECTION • Fasten flare nut with a torque wrench as specified in the table • When fastened too tight, flare nut may brake after a long period and cause refrigerant leakage. Indoor unit connection Connect both liquid and gas pipings to indoor unit. •...
  • Page 8 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibf/in 2 [0.5 to 0 kgf/cm2]). 6) Stop the emergency COOL operation. Press the E.O. SW twice to stop the operation. MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO...