GE 400 User Manual page 26

Sg series 400 & 500 kva / 480vac ul / s2
Hide thumbs Also See for 400:
Table of Contents

Advertisement

Home\Meter
INVERTER
f
L1
L2
L3
T
SYNCHRONIZED
Home\Meter
SYSTEM LOAD
L1
:
277 V
L2
:
277 V
L3
:
277 V
LOAD ON INVERTER
Home\Meter
SYSTEM LOAD
L1
: 75.0 kW
L2
: 60.1 kW
L3
: 45.0 kW
LOAD ON INVERTER
Home\Meter
MODULE LOAD
Total kVA
Percentage
LOAD ON INVERTER
Modifications reserved
OPM_SGS_USM_M40_M50_2US_V010.doc
60 Hz
277 V
277 V
277 V
+25° C
301.0 A
50 %
241.0 A
40 %
181.0 A
30 %
83.3 kVA
PF +/-0.90
66.7 kVA
PF +/-0.90
50.0 kVA
PF +/-0.90
200 kVA
40%
Inverter data screen
f
The output frequency of the Inverter.
L1
L2
3-phase output voltage PHASE/NEUTRAL.
L3
T
The temperature of the inverter bridge.
The synchronization status of the inverter with respect to
utility (SYNCHRONIZED / NOT SYNCHRONIZED).
Load on phases screen 1
... V
Output voltage PHASE/NEUTRAL for each phase.
... A
The output current as RMS values (for RPA: total
value of Parallel System).
... %
The output load as percentage (for RPA: with
respect to the rated power of Parallel System).
The source of the power supplied to the load:
- DETOUR ON (Q2 close)
- Q1 OPEN
- LOAD OFF
- ON BATTERY
Load on phases screen 2
... kW
The load active power (kW) (for RPA: total value of
Parallel System).
... kVA
The load apparent power (kVA) (for RPA: total
value of Parallel System).
... PF
The load power factor:
+ for inductive loads (lagging power factor).
- for capacitive loads (leading power factor).
The source of the power supplied to the load:
- DETOUR ON (Q2 close)
- Q1 OPEN
- LOAD OFF
- ON BATTERY
Module load screen
Total kVA
The load level in kVA (for RPA: only this unit).
Percentage
The load level as a percentage of the nominal rated load
(for RPA: only this unit).
The source of the power supplied to the load:
- DETOUR ON (Q2 close)
- Q1 OPEN
- LOAD OFF
- ON BATTERY
- LOAD ON INVERTER
- LOAD ON BYPASS
- LOAD ON BYPASS (eBoost)
- LOAD ON INVERTER
- LOAD ON BYPASS
- LOAD ON BYPASS (eBoost)
- LOAD ON INVERTER
- LOAD ON BYPASS
- LOAD ON BYPASS (eBoost)