Installer setting - function codes
Table 14 outlines the various customizable functions available to the Hydro Kit, along with their corresponding code values. Use the actual
low/actual High comments columns to log additional anomalies or comments related to the specific function code.
• All temperature values are stated in Fahrenheit.
• Altitude of region might impact Hydro Kit's ability to reach stated temperatures. Unit capability is rated at sea level.
Table 14: Installer Setting - Function Codes and Parameters
function
Disable 3 Minute Delay
Remote Air Sensor Connection
Celsius/Fahrenheit Switching
Setting Temperature Selection
Auto Dry Contact
Address Setting
Override Setting
Water Pump Test Run
Zone Temperature Setpoint
(Heating Mode)
Leaving Water Temperature
Setpoint
(Heating Mode)
Setting Water
(DHW) Tank Water
Temperature Setpoint
Setting Outdoor Temp. Range
Water Temperature Reset
Setting Indoor air Temp. Range
(Weather-dependent operation)
Setting leaving water Temp.
(Weather-dependent operation)
Setting start/maintain time
(Disinfection Operation)
DHW Tank Temperature
Deadband Setpoint*
(Lower Limit)
default
Value #1
02:01
01
03:01
01 : NOT connected
02 : Connected
04:01
01 : Celsius
02 : Fahrenheit
05:02
01 : Air Temperature
02 : Leaving Water Temperature
06:01
01 : Auto Start OFF
02 : Auto Start ON
07:00
00 ~ FF
08:00
00 : Slave
01 : Master
09:00
01 : Set
13:030:016
75 ~ 86
: Upper Limit of setting range
14:080:046
22 ~ 76
: Upper Limit of setting range
15:080:046
122 ~ 176
: Upper Limit of setting range
23:-10:015
50 - 68
: Upper Limit of setting range
24:021:016
68 ~ 86
: Upper Limit of setting range
25:080:046
149 ~ 176
: Upper Limit of setting range
26:000
00 : Disable
01 : Enable
26:006:023
01~07 : Starting Date
(01:Sun, 02:Mon, ····, 07:Sat)
27:070:010
104 ~ 129
: Maximum heating Temp.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Pre-coMMIssIoNING
Installer Setting Function Codes
Value #2
-
-
-
-
-
-
-
60 ~ 71
: Lower Limit of setting range
86 ~ 114
: Lower Limit of setting range
86 ~ 114
: Lower Limit of setting range
-4 ~ 41
: Lower Limit of setting range
60 ~ 66
: Lower Limit of setting range
104 ~ 129
: Lower Limit of setting range
-
00~23 hours
: Starting Time in 24 hours
05~60 min
: Maximum heating duration
Actual Low/Actual High
Comments
59