Download Print this page

Ordering Information; Technical Specifications - Bosch Appliances Smoke Alarm FLM325IM Modular Device

Contact module

Advertisement

2 | FLM‑325‑IM Contact Module
Data Circuit Length
Data (or polling) circuit length is the distance over the
circuit wire from the connection at the FACP to the most
distant device and back to the FACP. Data circuit length
must include the distance to any device connected to the
circuit in a T tap. The screw terminals can accept up to 14
AWG (1.5 mm) wire, but this reduces the allowable length
of the circuit.
Refer to the FPE‑1000‑SLC Installation Guide
(P/N: F01U078099) for specific wire instructions and
specifications for the FPA‑1000 series panels.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL-
listed normally open (NO) contact closure devices. Device
circuit wiring must not exceed 50 Ω. Install contact
closure devices according to the manufacturer's
installation instructions. All wiring must be supervised and
power-limited.
Note
Do not mix fire alarm initiating and
supervisory devices on the same module.
Parts Included
Quant.
Component
1
Point contact module
1
EOL resistor: Hochiki P/N 0400‑01046,. 10 kΩ, ¼ W, ¼ in.
1
Literature – Installation Guide

Technical Specifications

Electrical
SLC Applied Voltage (rated range):
SLC Current Consumption:
Resistance
End of Line Device
Initiating Device Circuit
Environmental
Environment:
Indoor dry
Relative Humidity:
Up to 90%, non‑condensing
Temperature:
Operating: 0°C to +49°C (+32°F to +120°F)
Storage: -30°C to +70°C (-22°F to +158°F)
Americas:
Europe, Middle East, Africa:
Bosch Security Systems, Inc.
Bosch Security Systems B.V.
130 Perinton Parkway
P.O. Box 80002
Fairport, New York, 14450, USA
5600 JB Eindhoven, The Netherlands
Phone: +1 800 289 0096
Phone: + 31 40 2577 284
Fax: +1 585 223 9180
Fax: +31 40 2577 330
security.sales@us.bosch.com
emea.securitysystems@bosch.com
www.boschsecurity.us
www.boschsecurity.com
© Bosch Security Systems 2011 | Data subject to change without notice
T7621673227 | Cur: en-US, V1, 25 May 2011
25.3 VDC to 39 VDC
Standby: 0.339 mA
Alarm: 0.358 mA
10 kΩ, 0.25 W per resistor
Less than 50 Ω
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.asia
Mechanical
Dimensions (H x W x D)
2.375 in. x 1.75 in. x 0.5 in.
(60.325 mm x 44.45 mm x 12.7 mm)
Weight
20 oz (0.567 kg)
Trademarks
Trademark names are used throughout this document. In
most cases, these designations are claimed as trademarks
or registered trademarks in one or more countries by their
respective owners. Rather than placing a trademark
symbol in every occurrence of a trademark name, Bosch
Security Systems, Inc. uses the names only in an editorial
fashion and to the benefit of the trademark owner with no
intention of infringing the trademark.
Hochiki is a trademark of Hochiki America Corporation.

Ordering Information

FLM‑325‑IM Contact Module
Allows compatible fire alarm control panels
(FACP) to supervise Form A or B dry contact
devices in a polling circuit
Represented by
FLM-325-IM