Parameter name
Com. Error
f850
selection
Com. Error
f851
detecting time
Reset function
f899
(Note 1) For setting the parameters, never duplicate the station address on the same communication line.
PLC rink relay register is automatically allocated according to the setting of the station address. As for the
setting of station addresses, consider the allocation of rink relay register that is determined by the other
station addresses and the number of words that have been set in the parameters f831 to f836, and
f841 to f846.
The maximum setting value for station address is 255, however when 255 is set, only one word of scan
data can be set. To set the scan data in its maximum value of 12 words, setting value of the station
address should be: 255-(12-1)= 244.
(Note 2) Setting of "free-run stop" is valid when the "operation command mode selection" [cmod] is
selected to the optional add-on cassette.
Setting of "deceleration stop" is valid when the "operation command mode selection" [cmod] is selected
to the optional add-on cassette or when the "speed setting mode selection" [fmod] is selected to the
optional add-on cassette. At the same time the deceleration stop returns the command of run/stop and the
speed reference value to 0. Except when the above command setting is selected, inverter cannot be
stopped.
Furthermore when the "operation command mode selection" [cmod] is set to other than the optional
add-on cassette and when the "speed setting mode selection" [fmod] is selected to the optional add-on
cassette, in some cases inverter can not stop running because of the setting of the parameters (zero-
speed operation setting). Torque control is valid when the "operation command mode selection" [cmod]
is set to the optional add-on cassette, but the inverter operation becomes "free-run stop" at that time.
Title
Setting value
0 to 4
0 to 1000
0, 1
Sets the inverter operation at time of communication error.
The action of inverter will be different depending on the
status (during operation or halt) of the inverter. (Note 2)
0: During halt
During operation
1: During halt
During operation
2: Invalid
3: During halt
During operation
4: During halt
During operation
Sets the time until the communication error is detected.
Setting is done by a unit of ms. (Note 3)
Resets the inverter station.
0: No action
1: To reset the inverter station. After resetting, setting
data returns to 0.
13
E6580772
Details
Inverter stops after free run.
Inverter trips.
Inverter stops after free run.
Inverter stops after free run.
(Setting is enabled with F10M
option connected.)
Inverter decelerates to stop.
Inverter decelerates to stop.
Inverter continues to run.
Inverter continues to run.