Hitachi L300P Series Quick Reference Manual page 31

Three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

"P" Group: Expansion Card Functions
Func.
Code
P001
Operation mode on expansion card #1 error
• 00 Trip (stop motor)
• 01 Continuous operation
P002
Operation mode on expansion card #2 error
• 00 Trip (stop motor)
• 01 Continuous operation
P044
DeviceNet comm watchdog timer
P045
Inverter action on DeviceNet comm error
• 00 Trip
• 01 Decelerate and trip
• 02 Hold last speed
• 03 Free run stop
• 04 Decelerate and stop
P046
DeviceNet polled I/O: Output instance number
P047
DeviceNet polled I/O: Input instance number
P048
Inverter action on DeviceNet idle mode
• 00 Trip
• 01 Decelerate and trip
• 02 Hold last speed
• 03 Free run stop
• 04 Decelerate and stop
P049
DeviceNet motor poles setting for RPM
P050
• Output frequency on analog reference signal
loss (–xFE2/–xFU2 models only)
• 00 Output freq. forced to 0 Hz; 500ms wait to
recover
• 01 Output freq. forced to 0 Hz; no wait to
recover
• 02 Output freq. forced to max. freq. A004
• 03 Output freq. forced to A020/A220
Name / Description
29
Default
Value
Set
–FE2/–FU2/
Value
–FR
00
00
1.00
01
21
71
01
0
00 / 00 / —