Rack airflow optimization kit
Hide thumbs Also See for 245161-B22 - 10642 42U Rack Shock Pallet:

Advertisement

4.
Gently push the foam rail gasket into the space until it is flush
with the vertical frame.
Installing foam rail gaskets between racks
CAUTION: The foam rail gasket must be installed into the
rack before two or more racks can be bayed together. For
additional information on baying racks, see the HP Baying
Rack Option Kit.
If installing the foam rail gasket between racks that have a baying kit
installed, the baying bracket must be removed before the foam rail
gasket can be inserted between the racks.
1.
Position the racks side by side.
2.
Cut the foam rail gasket to fit the size of your rack.
3.
Insert the foam rail gasket into the space between the racks
with the closed cell side of the foam rail gasket facing the front
of the rack.
NOTE: Follow steps 1 through 3 to install the foam rail
gasket into a rack that will be bayed using a 24-in.
baying bracket.
If the rack will be bayed using a 600-mm baying bracket,
rotate the foam rail gasket 90 degrees before inserting it
into the space between the racks.
4.
Gently push the foam rail gasket into the space between the
racks until it is flush with the vertical frame.
5.
(Optional) See the HP Baying Rack Option Kit for specific
information on baying racks.
Installing the floor gasket
1.
Depending on the size of your rack, cut the floor gasket at the
perforation to reduce the length from 800-mm (31 in) to 600-
mm (24 in).