Mv Room; Dqs-12/24 (Cvc) - Huawei JUPITER-3000K-H1 Smart User Manual

Transformer station
Hide thumbs Also See for JUPITER-3000K-H1 Smart:
Table of Contents

Advertisement

JUPITER-(3000K, 6000K, 9000K)-H1 Smart
Transformer Station
User Manual
No.
Item
4
(Optional)
Winding
thermostat
5
Off-load tap
changer
6
Dehydrating
breather
7
Oil level gauge
8
Pressure release
valve

2.4.4 MV Room

2.4.4.1 DQS-12/24 (CVC)

Issue 02 (2023-09-30)
Function
Measures and
controls the
transformer winding
temperature through
thermal simulation
by measuring the top
oil temperature.
Regulates the
voltage.
-
Indicates the oil level.
Releases pressure.
NO TE
No cable connector is installed in cabinet G1 or G3. The cable connectors in the figure are
for reference only. The actual position and dimensions may vary.
Copyright © Huawei Technologies Co., Ltd.
Description
The transformer winding temperature is
displayed through thermal simulation
technology, and the alarm and trip signals
are transmitted through the temperature
control switch.
There are five levels. Level 1 indicates the
maximum tapping value, level 3 indicates
the rated tapping value, and level 5
indicates the minimum tapping value.
The insulation oil is isolated from the
atmosphere through the airbag in the
conservator. The airbag is connected to the
atmosphere through the dehydrating
breather. The dehydrating breather contains
silica gel to absorb moisture and impurities
in the air and maintain good performance
of the insulation oil.
Indicates the oil level of the transformer oil
cabinet and reports the alarms of high and
low oil levels.
If a transformer is faulty, a large amount of
gas is generated, and the pressure of the
insulation oil increases sharply. When the
certain threshold is reached, the
transformer oil is discharged and the
internal pressure of the transformer
decreases to a normal value. At the same
time, a signal is sent to trip the circuit
breaker in the ring main unit.
2 Product Description
32

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jupiter-6000k-h1 smartJupiter-9000k-h1 smart

Table of Contents