Siemens SIMATIC ET 200SP Equipment Manual
Siemens SIMATIC ET 200SP Equipment Manual

Siemens SIMATIC ET 200SP Equipment Manual

Digital output module
Hide thumbs Also See for SIMATIC ET 200SP:

Advertisement

Quick Links

Edition
01/2024
EQUIPMENT MANUAL
SIMATIC
ET 200SP
Digital output module
DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0)
support.industry.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 1 Edition 01/2024 EQUIPMENT MANUAL SIMATIC ET 200SP Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) support.industry.siemens.com...
  • Page 2 Introduction Industrial cybersecurity SIMATIC Product overview ET 200SP Digital output module Wiring DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) Parameters/address space Equipment Manual Interrupts/diagnostics alarms Technical specifications Parameter data record 01/2024 A5E52818470-AA...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Table of contents Introduction............................ET 200SP Documentation Guide..................1.1.1 Information classes ET 200SP.................... 1.1.2 Basic tools........................1.1.3 MultiFieldbus Configuration Tool (MFCT)................1.1.4 SIMATIC Technical Documentation..................11 Industrial cybersecurity........................13 Introduction to industrial cybersecurity................13 Cybersecurity information....................13 Product overview..........................14 Properties.........................
  • Page 5: Introduction

    Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 6: 200Sp Documentation Guide

    This arrangement enables you to access the specific content you require. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742709). Basic information The System Manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP distributed I/O system.
  • Page 7 Product Information takes precedence over the device and system manuals. You can find the latest Product Information on the ET 200SP distributed I/O system on the Internet. (https://support.industry.siemens.com/cs/de/en/view/73021864) Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file.
  • Page 8: Basic Tools

    With the TIA Selection Tool , you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet. (https://support.industry.siemens.com/cs/ww/en/view/109767888) SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities on various SIMATIC S7 stations as bulk operations independent of TIA Portal.
  • Page 9 You can find SIEMENS PRONETA Basic on the Internet: (https://support.industry.siemens.com/cs/ww/en/view/67460624) SIEMENS PRONETA Professional is a licensed product that offers you additional functions. It offers you simple asset management in PROFINET networks and supports operators of automation systems in automatic data collection/acquisition of the components used through various functions: •...
  • Page 10: Multifieldbus Configuration Tool (Mfct)

    MultiFieldbus- and DALI-devices. In addition, the MFCT offers convenient options for mass firmware updates of ET 200 devices with MultiFieldbus- support and reading service data for many other Siemens devices. Functional scope of the MFCT • MultiFieldbus configuration:...
  • Page 11: Simatic Technical Documentation

    Online Support: Industry Online Support International https://support.industry.siemens.com/cs/ww/en/view/109742705 Watch this short video to find out where you can find the overview directly in Siemens Industry Online Support and how to use Siemens Industry Online Support on your mobile device: Quick introduction to the technical documentation of automation products per video ( https://support.industry.siemens.com/cs/us/en/view/109780491...
  • Page 12 Manuals, characteristics, operating manuals, certificates • Product master data You can find "mySupport" on the Internet. (https://support.industry.siemens.com/My/ww/en) Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
  • Page 13: Industrial Cybersecurity

    Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 14: Product Overview

    Product overview Properties Article number 6ES7132-6BH00-0CA0 (packing unit: 1 unit) View of the module 1 6 x 2 4 V D C /0 .5 A D IA G 24 V D C M A X . 10 A C C 0 0 B U : A 0 V 1.
  • Page 15 • Labeling strips • Color-coded labels • Reference identification label • Shield connection See also You can find more information on accessories in the ET 200SP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/58649293) System Manual. Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) Equipment Manual, 01/2024, A5E52818470-AA...
  • Page 16: Wiring

    This section contains the pin assignment for the module. You can find information on wiring the BaseUnit in the ET 200SP Distributed I/O System (http://support.automation.siemens.com/WW/view/en/58649293) System Manual. NOTE The load group of the module must begin with a light-colored BaseUnit. Also keep this in mind during configuration.
  • Page 17 You can also connect the ground and functional grounding via a potential distribution module (PotDis module) or AUX terminals. More information on potential distribution modules is available in the BaseUnits Equipment Manual (https://support.industry.siemens.com/cs/ww/en/view/59753521). NOTE You can use and combine the different connection options for all channels.
  • Page 18: Block Diagram

    Wiring 4.2 Block diagram Block diagram This section contains the schematic circuit diagram of the module. Figure 4-1  Schematic circuit diagram Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) Equipment Manual, 01/2024, A5E52818470-AA...
  • Page 19: Parameters/Address Space

    Parameters/address space Parameters Parameters for DQ 16x24VDC/0.5A HF You can specify the module properties with various parameters in the course of your STEP 7 configuration. The table below lists the configurable parameters. The efficiency range of the configurable parameters depends on the type of configuration. The following configurations are possible: •...
  • Page 20 Parameters/address space 5.1 Parameters Parameter Value range Default Configuration Scope with configuration soft­ in RUN ware, e.g. STEP 7 (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Channel activated • Disable Enable Channel Channel • Enable Reaction to CPU STOP • Turn off Turn off Channel Module...
  • Page 21: Explanation Of Parameters

    Parameters/address space 5.2 Explanation of parameters Explanation of parameters Diagnostics: No supply voltage L+ Enabling of the diagnostics for no or insufficient supply voltage L+. Diagnostics: Short circuit to ground Enabling of the diagnostics if a short circuit of the actuator supply to ground occurs. Diagnostics: Short circuit to L+ Enabling of the diagnostics if a short circuit of the actuator supply to L+ occurs.
  • Page 22 Specify on which slot a light-colored BaseUnit with supply voltage feed or a dark BaseUnit is located (see ET 200SP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/58649293) System Manual). All additional I/O modules of this potential group are plugged into dark-colored BaseUnits. You take the potential of the self-assembling voltage buses P1, P2 and AUX from the left neighbor.
  • Page 23: Address Space

    Parameters/address space 5.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image output/input. Configuration options of DQ 16x24VDC/0.5A HF You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure the module by means of a GSD file, the configurations are available under various short designations/module names;...
  • Page 24 (0 = value is incorrect). You can find more information on evaluating the value status in the ET 200SP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/58649293) System Manual. Address space for configuration as 1 x 16-channel DQ 16x24VDC/0.5A HF The figure below shows the address space assignment for configuration as a 1 x 16-channel module without value status.
  • Page 25 Parameters/address space 5.3 Address space Address space for configuration as 1 x 16-channel DQ 16x24VDC/0.5A HF, MSO For the configuration as a 1 x 16-channel module (module-internal Shared Output, MSO), channels 0 to 15 of the module are copied to up to four submodules. Channels 0 to 15 are then available with identical values in various submodules.
  • Page 26 Parameters/address space 5.3 Address space The figure below shows the assignment of the address space for submodules 1, 2, 3, and 4 and the value status. "IB" stands for input byte. "QB" stands for output byte. Assignment in the process image of the outputs (PIQ) for the 1st submodule 1st submodule (basic submodule): 7 6 5 4 3 2 1 0 QB a...
  • Page 27 Parameters/address space 5.3 Address space Address space for configuration as 2 x 8-channel DQ 16x24VDC/0.5A HF V1.0, S.2 The figure below shows the assignment of the address space for configuration as a 2 x 8-channel module without value status. Each of the two submodules has a freely assignable start address. "QB" stands for output byte. Figure 5-4  Address space for configuration as 2 x 8-channel DQ 16x24VDC/0.5A HF V1.0, S.2 without value status Address space for configuration as 2 x 8-channel DQ 16x24VDC/0.5A HF V1.0, S.2 QI...
  • Page 28 Parameters/address space 5.3 Address space Address space for configuration as 4 x 4-channel DQ 16x24VDC/0.5A HF V1.0, S.4 The figure below shows the address space assignment for configuration as a 4 x 4-channel module without value status. Each of the four submodules has a freely assignable start address. "QB" stands for output byte.
  • Page 29 Parameters/address space 5.3 Address space Address space for configuration as 4 x 4-channel DQ 16x24VDC/0.5A HF V1.0, S.4 QI The figure below shows the address space assignment for configuration as a 4 x 4-channel module with value status. Each of the four submodules has a freely assignable start address. "IB" stands for input byte. "QB"...
  • Page 30: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error displays LED displays The figure below shows the LED displays (status and error displays) of the module: ① DIAG (green/red) ② Channel status and channel error (green) ③ PWR (green) Figure 6-1  LED displays Meaning of the LEDs The following tables explain the meaning of the status and error displays.
  • Page 31 Interrupts/diagnostics alarms 6.1 Status and error displays DIAG LED Table 6-1  Error display of the DIAG LED DIAG LED Meaning Backplane bus supply of the system is interrupted or switched off. Module not configured Flashes Module parameters assigned and no module/channel diagnostics available Module parameters assigned and module/channel diagnostics available Flashes Channel status and channel error LEDs...
  • Page 32 Interrupts/diagnostics alarms 6.1 Status and error displays The figure below shows an example of a cycle (8 seconds) consisting of a sequence of channel status phase, transition, channel error phase, and renewed transition. ① Status display ② Transition indicated by high-frequency flashing of all LEDs ③...
  • Page 33: Interrupts

    Interrupts/diagnostics alarms 6.3 Diagnostics alarms Interrupts The DQ 16×24VDC/0.5A HF digital output module supports diagnostic interrupts. Diagnostics interrupts The module generates a diagnostic interrupt for the following events: • Short circuit • Wire break • Parameter assignment error • Supply voltage missing •...
  • Page 34 Interrupts/diagnostics alarms 6.3 Diagnostics alarms Diagnostics alarm Error code Meaning Solution Parameter assignment • The module cannot evaluate parameters Correct the parameter assignment error for the channel • Incorrect parameter assignment Supply voltage miss­ No or insufficient supply voltage L+ •...
  • Page 35: Technical Specifications

    Technical specifications Technical specifications of the DQ 16x24VDC/0.5A HF The following table shows the technical specifications as of 01/2024. You will find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/ww/en/pv/6ES7132-6BH00-0CA0/td?dl=en). Article number 6ES7132-6BH00-0CA0 General information  ...
  • Page 36 Technical specifications 7.1 Technical specifications Article number 6ES7132-6BH00-0CA0 Supply voltage   Rated value (DC) 24 V permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Input current   Current consumption, max. 20 mA; without load output voltage / header  ...
  • Page 37 Technical specifications 7.1 Technical specifications Article number 6ES7132-6BH00-0CA0 Load resistance range   • lower limit 48 Ω upper limit 12 kΩ • Output current   • for signal "1" rated value 0.5 A • for signal "0" residual current, max. 0.1 mA Output delay with resistive load  ...
  • Page 38 Technical specifications 7.1 Technical specifications Article number 6ES7132-6BH00-0CA0 Alarms   • Diagnostic alarm Diagnoses   Monitoring the supply voltage • • Wire-break Yes; channel by channel • Short-circuit to M Yes; channel by channel • Short-circuit to L+ Yes; channel by channel •...
  • Page 39 Technical specifications 7.1 Technical specifications Residual current for signal state "0" NOTE Residual current for signal state "0" Due to the Diagnostics: Wire break function, there is a low level of residual current at an activated check for wire break in the "0" signal state at the output. This may cause the display diodes to flicker.
  • Page 40 5 mH 10 mH 30 mH 50 mH 100 mH 300 mH 500 mH 1152 mH Figure 7-2  Maximum switching frequency Dimension drawing See Equipment Manual ET 200SP BaseUnits (https://support.industry.siemens.com/cs/ww/en/view/59753521) Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) Equipment Manual, 01/2024, A5E52818470-AA...
  • Page 41: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reparameterize the module in your user program, regardless of your programming. This means that you can use all the functions of the module even if you configured it via PROFIBUS-GSD.
  • Page 42 Parameter data record A.1 Parameter assignment and structure of parameter data record Data record structure Figure A-1  Structure of data record 128 or data records 64 to 79 Header information The figure below shows the structure of the header information. Figure A-2  Header information Digital output module DQ 16x24VDC/0.5A HF (6ES7132-6BH00-0CA0) Equipment Manual, 01/2024, A5E52818470-AA...
  • Page 43: Error Codes

    Parameter data record A.2 Error codes Parameter The figure below shows the structure of the parameters for channels 0 to 15. You enable a parameter by setting the corresponding bit to "1". Byte x*/** Enable diagnostics No supply voltage L+ Short circuit to ground Short circuit to L+ Diagnostics: Wire break Check for wire break...
  • Page 44 Parameter data record A.2 Error codes Error code in STATUS parameter Meaning Solution (hexadecimal) Byte 0 Byte 1 Byte 2 Byte 3 Module not accessible. • Check station. • Plug the module in correctly. • Check parameters of the WRREC block. Header error (version or specified bits incor­...

This manual is also suitable for:

6es7132-6bh00-0ca0

Table of Contents