Neutral Mode: With Display/ Without Display
The LED behavior of Neutral mode Temperature readings are shown below:
LED Behavior
White on
White Breath
White Blink
Threshold settings of LED color rings:
Air Quality Score
Temperature
Humidity
CO
TVOC
PM 2.5
* These threshold parameters can be configured as per requirement. For example,
TVOC parameter threshold can be configured as Good (<500ppb), medium(500-
1500ppb),poor(>1500ppb) as per UBA study by the German Federal Environmen-
tal Agency. Just need to set the following two parameters (Take BACnet point as
an example): CfgAlarmTVOCHighLimit =500 CfgAlarmTVOCHighHigh
Limit =1500. There will be time delay (default 60 seconds) to stabilize the change
between different color.

3.1.3 Parameter Description

The TR50 IAQ Sensor device will show 5 different parameter readings on the LCD
display.
12
Air Quality Level
Good
Medium
Poor
Air Quality Parameters*
2
Sensor Reading Level
Good
Medium
Poor (For CO2, PM2.5 and TVOC)
Green
(Good)
>80
40-80
o
------
<65
F or >86
------
<10% or >80%
<1000 ppm
1000-1400 ppm
<250 ppb
250-350 ppb
3
<35 µg/m
35-55 µg/m
Sensor Health
-
-
Sensor Failure
Yellow
(Medium)
<40
o
F
>1400 ppm
>350 ppb
3
>55 µg/m
TR50 - User Guide
Red
(Poor)
3